UNIT 5: Power System Protection - Exam-Focused Short Notes
I. FAULT ANALYSIS & SYMMETRICAL COMPONENTS
Types of Faults & Characteristics
-
Symmetrical (Balanced) Fault: Three-phase short circuit (L-L-L). System remains balanced; analyzed using only positive sequence network.
-
Unsymmetrical (Unbalanced) Faults:
-
Single Line-to-Ground (L-G): Most common (~70%). Requires all three sequence networks in series.
-
Line-to-Line (L-L): No ground involvement. Positive & negative sequence networks in parallel.
-
Double Line-to-Ground (L-L-G): All three sequence networks in parallel.
-
Causes: Insulation failure, weather, human error, equipment damage.
-
Effect: System unbalance, voltage collapse, stability threat, high mechanical stress.
-
Fault Current Calculation (Generator Terminal)
For an unloaded generator with solidly grounded neutral:
- L-G Fault:
$$I_f = \frac{3E}{X_1 + X_2 + X_0}$$
> [!TIP] **Key Point:** Zero sequence path exists only if neutral is grounded.
- L-L-G Fault:
$$I_f = \frac{\sqrt{3}E}{X_1 + \frac{X_2 X_0}{X_2 + X_0}}$$
- L-L Fault:
$$I_f = \frac{\sqrt{3}E}{X_1 + X_2}$$
- L-L-L Fault:
$$I_f = \frac{E}{X_1}$$
Fault Level / Fault MVA:
$$\text{Fault MVA} = \sqrt{3} \times V_{\text{base}} \times I_{\text{fault}}$$
. It's the maximum short-circuit power a breaker must interrupt at a point.
Symmetrical Components Theory
-
Purpose: Decouple unbalanced 3-phase system into three balanced 3-phase systems (Positive, Negative, Zero Sequence).
-
Sequence Networks: Equivalent impedance diagrams for each sequence.
-
Positive Sequence: Normal rotation (A-B-C). All generators have synchronous (Xd), transient (X'd), sub-transient (X"d) reactances.
-
Negative Sequence: Reverse rotation (A-C-B). Reactance ≈ X"d for generators; for transformers, same as positive sequence but phase-shifted.
-
Zero Sequence: All phases in phase (A+A+A). Path requires grounded neutral. For transformers: zero seq. impedance depends on winding connection (star/delta) and grounding.
-
| Fault Type | Sequence Network Interconnection |
|---|---|
| L-G | Series: $$\displaystyle Z_1 + Z_2 + Z_0 $$ |
| L-L | Parallel: $$\displaystyle Z_1 \parallel Z_2 $$ |
| L-L-G | Parallel: $$\displaystyle Z_1 \parallel Z_2 \parallel Z_0 $$ |
| L-L-L | Only $$\displaystyle Z_1 $$ |
Per-Unit System & Reactances
- Convert all impedances to common base MVA & base kV.
$$Z_{\text{p.u.}}^{\text{new}} = Z_{\text{p.u.}}^{\text{old}} \times \frac{(\text{MVA}_{\text{base}}^{\text{new}} / \text{MVA}_{\text{base}}^{\text{old}})}{(kV_{\text{base}}^{\text{new}} / kV_{\text{base}}^{\text{old}})^2}$$
-
Reactance Significance:
-
X"d (Sub-transient): Fault current initial value (first 1-2 cycles). Used for protection sizing.
-
X'd (Transient): Fault current after sub-transient decay (up to ~0.5 sec). Used for stability studies.
-
Xd (Synchronous): Steady-state fault current. Rarely used for protection.
-
X2 (Negative): ≈ X"d for generators.
-
X0 (Zero): Often < X1 for generators with grounded neutral; critical for L-G fault magnitude.
-
II. PROTECTIVE RELAYS: TYPES, PRINCIPLES & CHARACTERISTICS
Fundamental Relay Operating Principles
-
Electromagnetic Attraction Type: AC/DC. Plunger attracted to solenoid. Used for overcurrent, under-voltage.
-
Induction Type Relays (AC only):
-
Induction Disc Relay:
-
Construction: Aluminum disc in magnetic field from two electromagnets (fluxes 90° apart).
-
Torque Equation: $$\displaystyle T = K \phi_1 \phi_2 \sin \theta $$. Disc rotates until spring torque balances.
-
Application: Overcurrent, directional, distance relays.
-
Minimize Overrun: Use brake magnet (permanent magnet) to create retarding torque proportional to speed.
-
-
Induction Cup Relay:
-
Construction: Hollow cylindrical cup (Al/Cu) instead of disc. Faster, more sensitive.
-
Reset-to-Pickup Ratio: Very high (0.9-0.95). Disc relay: low (~0.85). Cup relay preferred for differential protection where high reset ratio prevents unwanted operation on through-fault CT saturation.
-
-
Relay Characteristics & Plots (R-X Plane)
| Relay Type | Characteristic Shape | Directionality | Primary Application |
|---|---|---|---|
| Impedance Relay | Circle centered at origin. $$\displaystyle Z = \frac{V}{I} $$ | Non-directional (needs separate directional element) | Distance Protection (Zone 1) |
| MHO Relay | Circle passing through origin. $$\displaystyle Z = \frac{V}{I - I \cdot k} $$ (offset) | Inherently directional (characteristic lies in 1st/3rd quadrants) | Distance Protection (main relay) |
| OFF-SET MHO | Larger circle, offset further. More resistive reach. | Directional | Distance Protection (Zone 2/3, long lines) |
| Directional Relay | Semicircle/quadrilateral in operating region. | Yes (compares phase angle) | Backup, differential schemes |
Distance Relay Zones:
- Zone 1: 80-90% of line length. Instantaneous.
- Zone 2: 100-120% of line + next line's 50%. Time-delayed.
- Zone 3: 100-120% of line + next line + backup. Longest time delay.
Time-Current Characteristics: IDMT
-
Principle: Operating time inversely proportional to fault current magnitude.
-
Standard Equation (IEC):
$$t = \frac{\text{TMS} \times \beta}{(I_f / I_{\text{ps}})^\alpha - 1}$$
Where:
* $$\displaystyle I_f $$ = Fault current
* $$\displaystyle I_{\text{ps}} = (\text{Plug Setting}) \times \text{Relay Rated Current} $$
* TMS = Time Multiplier Setting (0.1 to 1.0)
* $\alpha, \beta$ = Standard constants (for normal inverse: $$\displaystyle \alpha=0.02, \beta=0.14 $$; very inverse: $$\displaystyle \alpha=1, \beta=13.5 $$; extremely inverse: $$\displaystyle \alpha=2, \beta=80 $$)
IDMT Calculation Steps:
- Find $$\displaystyle I_{\text{ps}} $$ from plug setting % and relay CT primary rating.
- Compute $$\displaystyle (I_f / I_{\text{ps}}) $$.
- Use standard TMS curve equation or graph to find $t$.
Static & Numerical Relays
-
Static Relays (Electronic):
-
Advantages: No moving parts, fast, adjustable characteristics, low burden, can implement complex logic.
-
Functional Blocks:
-
Level Detector: Outputs 1 if input > set value. Functional Diagram: Comparator + hysteresis ( Schmitt Trigger).
-
Comparator: Compares two inputs.
-
Amplitude Comparator: $$\displaystyle |A| > |B| $$? Output = 1.
-
Phase Comparator: $$\displaystyle \angle A - \angle B < \theta $$? Output = 1.
-
Conversion: Use quadrature transformer to convert phase comparison to amplitude comparison (and vice versa).
-
-
-
-
Microprocessor-Based / Numerical Relays:
-
Block Schematic:
Analog Inputs→Filter & Anti-alias→ADC (Sampling)→CPU (DSP)→Output Logic→Trip Signal -
Functions: All EM relay functions + fault location, communication, self-monitoring, event recording.
-
Software Development: Follows IEC 61850 standards for interoperability, security (cyber), and reliability (redundancy, watchdogs).
-
III. PROTECTION SCHEMES FOR POWER SYSTEM ELEMENTS
Generator / Alternator Protection
| Fault Type | Protection Scheme | Key Feature |
|---|---|---|
| Stator Phase Faults | Percentage Differential | Biased (slope). CT mismatch & through-fault stability. |
| Stator Ground Fault | Residual Overcurrent (for high resistance grounding) | Sensitive ground CT. |
| Rotor Ground Fault | Insulation Monitoring | DC voltage injection. |
| Rotor Overheat/Loss of Excitation | Loss of Excitation Relay (MHO characteristic) | Detects reactive power import. |
| Incipient Faults | Buchholz Relay | Gas accumulation (minor) or oil surge (major). |
| Overspeed/Overcurrent | Overcurrent/Reverse Power | Mechanical/electrical stress. |
-
Percentage Differential Protection (Stator):
-
Slope: 15-30%. Higher slope for larger generators.
-
Operation: $$\displaystyle I_{\text{operating}} = |I_1 - I_2| $$, $$\displaystyle I_{\text{restraint}} = \frac{|I_1|+|I_2|}{2} $$. Trip if $$\displaystyle I_{\text{op}} > \text{Slope} \times I_{\text{res}} + I_{\text{min}} $$.
Problem: Given CT currents, slope, and $$\displaystyle I_{\text{min}} $$, decide trip.
-
-
Buchholz Relay:
-
Location: In conservator pipe between tank & conservator.
-
Operation:
-
Incipient Fault: Gas bubbles rise → float lowers → alarm contact.
-
Severe Fault: Oil surge → baffle plate deflects → trip contact.
-
-
Detects: Turn-to-turn faults, core hot spots, oil level fall.
-
Transformer Protection
-
Merz-Price (Percentage Differential) for Transformer:
-
Challenge: Star-Delta connection causes phase shift & CT ratio mismatch.
-
Solution: Choose CT ratios so that secondary currents are equal in magnitude and phase under normal conditions.
-
CT Ratio Calculation (Star-Delta):
-
$$\text{CT Ratio}_{\text{Star}} = \frac{\text{Transformer kV}_{\text{Star}}}{\text{Base kV}} \times \frac{\text{Transformer MVA}}{\text{Base MVA}} \times \frac{\text{CT secondary}}{\text{Relay CT rating}}$$
$$\text{CT Ratio}_{\text{Delta}} = \frac{\text{Transformer kV}_{\text{Delta}}}{\text{Base kV}} \times \frac{\text{Transformer MVA}}{\text{Base MVA}} \times \frac{\sqrt{3} \times \text{CT secondary}}{\text{Relay CT rating}}$$
> **Key:** Delta side CTs are connected in **star** (or vice versa) to compensate for vector group.
-
Other Protections:
-
Restricted Earth Fault (REF): Sensitive ground fault protection for transformer neutral zone.
-
Buchholz: For oil-filled transformers.
-
Overcurrent/Overfluxing: External backup.
-
Transmission Line Protection
-
Distance Protection: Primary. Uses impedance relays. Three zones with time-graded coordination.
-
Pilot Protection Schemes: Fast, selective for entire line length. Requires communication channel (pilot).
-
Power Line Carrier (PLC):
-
Implementation: High-frequency (30-500 kHz) signal coupled to power line via coupling capacitor & line trap.
-
Voltage Range: Typically 33 kV to 220 kV.
-
Merits: No separate wire, uses existing line.
-
Demerits: Attenuation, noise, requires line filters, not for EHV (>400 kV).
-
Phase Comparison Scheme: Compare phase angles of currents at both ends. Trip if both ends see fault (internal). Block if only one end sees fault (external).
-
-
Busbar Protection
-
Differential Protection: All incoming/outgoing CTs sum to zero under normal/external fault. Any imbalance → trip. Requires CTs with same ratio & characteristic.
-
Frame Leakage Protection:
-
Principle: CT surrounds busbar support frame. Under bus fault, current flows through frame to ground → operates relay.
-
Application: Simple, used for small, important busbars.
-
Current Limiting Reactors
-
Purpose: Limit fault current magnitude to within breaker capacity during faults.
-
Types: Air-core (dry, no saturation) or iron-core.
-
Application: Connected in series with generators, feeders, or bus sections.
-
Location: Often in generator leads to limit fault current from that generator.
IV. CIRCUIT BREAKERS: THEORY, TYPES & SELECTION
Arc Phenomenon & Interruption Theory
-
Arc Formation: When contacts separate, ionization of medium creates low-resistance path.
-
Arc Quenching: Critical for interruption. Methods: High pressure, cooling, lengthening, dielectric strength increase.
-
Theory of Current Interruption (Energy Balance):
-
Before Current Zero: Power input from source = Power loss in arc ($$\displaystyle I^2R $$) + Rate of energy storage in arc ($dW/dt$).
-
At Current Zero: $dW/dt$ must be negative (arc loses energy) for thermal reignition to be avoided.
-
After Current Zero: Dielectric strength of medium must rise faster than recovery voltage across contacts.
-
-
Recovery Voltage vs. Restriking Voltage:
-
Restriking Voltage: Transient voltage appearing across contacts immediately after current zero. High-frequency oscillation. Dangerous (can cause re-ignition).
-
Recovery Voltage: Steady-state voltage across CB after transient dies down. Must be withstood by CB.
-
Circuit Breaker Ratings & Selection
- Breaking Capacity: Max symmetrical RMS current it can interrupt at rated voltage. Based on first-cycle (sub-transient) fault current.
$$\text{Breaking Capacity (MVA)} = \sqrt{3} \times V_{\text{rated}} \times I_{\text{breaking}}$$
> Must be > **maximum fault level** at installation point.
- Making Capacity: Max peak current it can close onto a 3-phase bolted fault. Higher than breaking capacity (includes DC component).
$$\text{Making Capacity (kA peak)} = \sqrt{2} \times [1 + e^{-t/\tau}] \times I_{\text{sym}}$$
Where $t$ = closing time, $\tau$ = time constant of circuit.
- Selection Criteria: Rated voltage/current, fault level, duty (number of operations), application (transmission, distribution, industrial), environment.
Types of Circuit Breakers & Comparison
| Type | Arc Quenching Medium | Principle | Voltage Range | Key Advantages | Key Disadvantages |
|---|---|---|---|---|---|
| Oil (Bulk/Minimum) | Mineral Oil | Explosion pot (decomposition gas creates pressure) | Up to 400 kV | Good insulation, old tech. | Fire risk, maintenance, pollution. |
| Air Blast (ABCB) | Compressed Air | High-velocity air blast elongates & cools arc. | 132-400 kV | Fast, no fire, suitable for autoreclose. | Current chopping, overvoltages, complex. |
| SF6 | SF6 Gas | Puffer/Self-blast: Gas compressed, flows through arc. | 72.5 kV to 800 kV | Excellent dielectric, very fast, quiet, low maintenance. | Gas leakage, moisture sensitivity, cost. |
| Vacuum (VCB) | Vacuum ($$\displaystyle 10^{-6} $$ torr) | Arc in vacuum extinguished when contacts separate (metal vapor condenses). | Up to 38 kV (common), up to 145 kV | Very fast, long life, no maintenance, eco-friendly. | Limited voltage rating, requires high vacuum. |
| HRC Fuse | Sand/Fused silica | Fuse element melts under fault current, sand quenches arc. | LT (415 V) | Very fast, cheap, simple. | Single-use, needs replacement. |
Explosion Pot (Oil CB):
- Plain/Cross-jet: Simple, limited breaking capacity.
- Self-Blast: Uses arc energy to generate pressure. More efficient.
- Oil Turbine: Uses mechanical turbine to blast oil.
V. ADVANCED & MISCELLANEOUS TOPICS
Security & Reliability in Protection Systems
-
Security: No tripping for non-faults (dependability inverse). Ensured by:
-
Redundancy (dual systems, voting logic).
-
Supervision (watchdog timers, self-checks).
-
Proper coordination (settings, zones).
-
-
Reliability: Tripping for all faults (security inverse). Ensured by:
-
Diversity (different operating principles).
-
High-quality components (CTs, relays).
-
Regular testing & maintenance.
-
Specific Relay Applications Summary
| Relay Type | Recommended Application | Reason |
|---|---|---|
| Induction Disc | Overcurrent, Directional, Distance (older systems) | Robust, simple, moderate reset ratio. |
| Induction Cup | Differential, High-speed applications | High reset ratio (0.9-0.95), fast, sensitive. |
Integrated System Concepts
-
Role of Protection: First line of defense for system stability. Must be fast, selective, reliable.
-
Software Development for Protection:
-
Lifecycle: Requirements → Design → Coding (IEC 61131-3/61850) → Testing (hardware-in-loop) → Validation → Maintenance.
-
Security: Cyber-security protocols, secure communication (IEC 62351).
-
Reliability: Redundant processors, watchdog timers, fail-safe design.
-
Logic Circuits in Relays: Improve functions by implementing timers, latches, voting (2-out-of-3), blocking signals to enhance security and selectivity.
END OF UNIT 5 NOTES