EX-701 · Power System Protection/Unsolved PYQ Paper

EX-701 Power System Protection - Nov 2022 Question Paper

Under each question, How to answer lists the points an answer should cover, outlined by CampusPrep from the syllabus. Check the details against your textbook.

  1. 7 Marks
    aExplain Reverse power relay with neat sketch add all minute constructional detail.
    How to answer
    • Definition and operating principle of reverse power relay (directional power).
    • Constructional details: voltage coil, current coil, disc/cup, contacts, spring.
    • Neat labelled sketch and phasor explanation.
    • Applications in generator / parallel feeder protection.
  2. 7 Marks
    bWhat do you understand by the term 'PILOT' in context with power line protection? Explain the concept of power line carrier protection.
    How to answer
    • Meaning of PILOT in power line protection (communication channel).
    • Types of pilot: wire pilot, carrier, microwave, fibre.
    • Concept of power line carrier protection with block diagram.
    • Transmitter, receiver, coupling and trapping explanation.
  3. 7 Marks
    aIn a short circuit test on a 3 pole, $110\,kV$ circuit breaker, power factor of the fault was $0.4$, the recovery voltage was $0.95$ times full line value. The breaking current was symmetrical. The frequency of oscillation of restriking voltage was $15000 c/s$. estimate the average rate of rise of restriking voltage. The neutral is grounded and the fault involves earth.
    How to answer
    • Formula for peak restriking voltage with grounded neutral and recovery voltage factor.
    • Frequency of oscillation $f = 15000$ c/s and power factor effect.
    • Average RRRV = peak voltage / time to peak.
    • Substitute $110\,kV$, $0.95$ factor, $0.4$ pf to estimate value.
  4. 7 Marks
    bDiscuss about comparators and level detectors in brief.
    How to answer
    • Definition of comparator and level detector in static relays.
    • Types: amplitude and phase comparators.
    • Basic op-amp / transistor circuits.
    • Role in distance, overcurrent static relays.
  5. 7 Marks
    aExplain in detail the Effect of arc resistance and power swings on performance of distance relay.
    How to answer
    • Impedance seen by distance relay with arc resistance $R_{arc}$.
    • Shift of impedance locus on R-X diagram.
    • Effect of power swings on apparent impedance and maloperation.
    • Use of blinder / PSB to mitigate.
  6. 7 Marks
    bA generator of negligible resistance having $1.0$ per unit voltage behind transient reactance is subjected to different types of faults. Such as for 3 phase fault the resulting fault current in per unit is $3.33$ for line to line fault it is $2.23$ and for line to ground fault it is $3.01$. Calculate the per unit values of 3 sequence reactances.
    How to answer
    • Fault current formulas for 3-phase, L-L and L-G faults in symmetrical components.
    • Use $I_{3\phi}=3.33$, $I_{L-L}=2.23$, $I_{L-G}=3.01$ pu with $E=1.0$ pu.
    • Solve for $X_1$, $X_2$, $X_0$ sequence reactances.
    • Check values and units in per unit.
  7. 7 Marks
    aAdvantages of static relays over electromagnetic relays.
    How to answer
    • Low burden, fast operation, no moving parts.
    • High sensitivity, accuracy and reset ratio.
    • Less maintenance and wide setting range.
  8. 7 Marks
    bProperties of SF6 which makes it suitable for circuit breaker.
    How to answer
    • High dielectric strength and arc quenching property of SF6.
    • Electronegativity, thermal conductivity, chemical stability.
    • Suitability for high voltage circuit breaker application.
  9. 7 Marks
    a

    An IDMT type over current relay is used to protect a feeder through $500/1$ Amp CT. the relay has a PS of $125\%$ and TMS $= 0.3$. find the time of operation of the said relay if a fault current of $5000\,A$ flows through the feeder. Make use of following characteristic

    PSM : 2 3 5 8 10 15
    Time for unity TMs 10 6 4.5 3.2 3 2.5

    ($100\%$ current $= 1\,A$).

    How to answer
    • Calculate relay pickup current from CT ratio $500/1$ A and PS $125\%$.
    • Calculate PSM = fault current / pickup current.
    • Obtain time for unity TMS from given PSM vs time table by interpolation.
    • Actual operating time = tabulated time $\times$ TMS $0.3$.
  10. 7 Marks
    bExplain in detail the transmission line protection in terms of current, time grading and distance.
    How to answer
    • Principle of current grading and time grading with relay settings.
    • Distance protection zones and reach settings.
    • Comparison of three schemes with diagrams.
    • Advantages for transmission line selectivity.
  11. 14 Marks
    [Question 6 not visible in provided scans - printed on missing pages 3-4]
    How to answer
    • Content not available in scans.
  12. 14 Marks
    [Question 7 not visible in provided scans - printed on missing pages 3-4]
    How to answer
    • Content not available in scans.
  13. 14 Marks
    [Question 8 not visible in provided scans - printed on missing pages 3-4]
    How to answer
    • Content not available in scans.