Skip to content
EX-701 · Power System Protection/Quick Revision Short Notes

Power System Protection (EX-701) - Unit 4 Short Notes

UNIT 4: POWER SYSTEM PROTECTION - EXAM-FOCUSED SHORT NOTES


I. FAULT ANALYSIS & SYMMETRICAL COMPONENTS

Types of Power System Faults

  • Symmetrical Fault: Three-phase fault (LLLG). All phases affected equally. System remains balanced. Highest fault current.

  • Unsymmetrical Faults:

    • Single Line-to-Ground (SLG/LG): Most common (~70%).

    • Line-to-Line (LL): Second most common.

    • Double Line-to-Ground (DLG/LLG):

  • Fault Level / Fault MVA: The maximum power (in MVA) that can flow into a fault at a given point. It determines the required breaking capacity of circuit breakers.

$$ \text{Fault MVA} = \sqrt{3} \times V_{\text{base}} \times I_{\text{fault}} $$

Symmetrical Components (Krenz's Theorem)

  • Significance: Any set of three unbalanced phasors (voltages/currents) can be resolved into three sets of balanced phasors:

    1. Positive Sequence ($$\displaystyle V_1, I_1 $$): Balanced, phase sequence A-B-C.

    2. Negative Sequence ($$\displaystyle V_2, I_2 $$): Balanced, phase sequence A-C-B.

    3. Zero Sequence ($$\displaystyle V_0, I_0 $$): All three phasors in phase.

  • Simplification: Allows analysis of complex unsymmetrical faults by solving three simple, independent, balanced systems.

Sequence Networks

  • Positive Sequence Network: Represents the normal balanced system. Contains internal EMFs ($$\displaystyle E_f $$). Reactance = $$\displaystyle X_d'' $$ (sub-transient) for generators during faults.

  • Negative Sequence Network: No internal EMFs ($$\displaystyle E_2 = 0 $$). Reactance = $$\displaystyle X_d'' $$ (for synchronous machines, often same as positive sequence for faults).

  • Zero Sequence Network: Path depends on grounding. For a generator with solidly grounded neutral, $$\displaystyle Z_0 = Z_{g} + 3Z_n $$ (where $$\displaystyle Z_g $$ is generator zero seq. reactance, $$\displaystyle Z_n $$ is neutral grounding impedance). No zero sequence current flows if neutral is isolated.

Fault Current Derivation (at Generator Terminals, Unloaded, Solid Ground)

General Method: Interconnect sequence networks based on fault type. Solve for $$\displaystyle I_0, I_1, I_2 $$. Fault currents are derived from these.

  1. Single Line-to-Ground (SLG) Fault (Phase A to Ground):

    • Connection: Series: $$\displaystyle Z_1 + Z_2 + Z_0 $$.

    • Sequence Current:

$$ I_1 = I_2 = I_0 = \frac{E_f}{Z_1 + Z_2 + Z_0} $$

*   **Fault Current (Phase A):** 

$$ I_f = I_a = 3I_0 = \frac{3E_f}{Z_1 + Z_2 + Z_0} \boxed{} $$

  1. Line-to-Line (LL) Fault (Phase B & C):

    • Connection: Parallel: $$\displaystyle I_1 = -I_2 $$, $$\displaystyle I_0 = 0 $$. Networks in parallel: $$\displaystyle Z_1 + Z_2 $$.

    • Sequence Current:

$$ I_1 = -I_2 = \frac{E_f}{Z_1 + Z_2} $$

*   **Fault Current (e.g., $$\displaystyle I_b $$):** 

$$ I_f = I_b = \sqrt{3} I_1 \angle 30^\circ \boxed{} $$

  1. Double Line-to-Ground (DLG) Fault (Phases B & C to Ground):

    • Connection: $$\displaystyle I_1 + I_2 + I_0 = 0 $$. Networks in parallel: $$\displaystyle Z_1 \parallel (Z_2 + Z_0) $$.

    • Sequence Currents:

$$ I_1 = \frac{E_f}{Z_1 + \frac{Z_2 Z_0}{Z_2 + Z_0}} $$

$$ I_2 = -I_1 \frac{Z_0}{Z_2 + Z_0}, \quad I_0 = -I_1 \frac{Z_2}{Z_2 + Z_0} $$

*   **Fault Current (Phase A):** 

$$ I_a = 0, \quad I_b = I_1 (\sqrt{3} \angle 30^\circ - \frac{Z_2}{Z_2+Z_0}), \quad I_c = I_1 (\sqrt{3} \angle -30^\circ - \frac{Z_0}{Z_2+Z_0}) $$

  1. Three-Phase Fault (LLLG):

    • Connection: Only positive sequence network. $$\displaystyle I_1 = E_f / Z_1 $$, $$\displaystyle I_2 = I_0 = 0 $$.

    • Fault Current:

$$ I_f = I_a = I_1 = \frac{E_f}{Z_1} \boxed{} $$

Effect of Fault Impedance ($$\displaystyle Z_f $$)

  • Adds to the impedance in the fault path.

  • SLG Fault: $$\displaystyle I_f = \frac{3E_f}{Z_1 + Z_2 + Z_0 + 3Z_f} $$

  • LL Fault: $$\displaystyle I_f = \frac{\sqrt{3} E_f}{Z_1 + Z_2 + Z_f} $$

  • DLG Fault: $$\displaystyle Z_f $$ appears in parallel with $$\displaystyle Z_0 $$ in the negative-zero sequence loop.

  • Result: Fault current decreases as $$\displaystyle Z_f $$ increases.

System Representation for Fault Studies

  • Per-Unit System: Simplifies calculations by eliminating voltage/transformer ratio conversions.

  • Base Quantity Selection: Choose common $$\displaystyle S_{base} $$ and $$\displaystyle V_{base} $$ for the entire system.

  • Conversion of Reactances:

$$ X_{\text{p.u., new}} = X_{\text{p.u., old}} \times \frac{(S_{base,\ \text{new}} / S_{base,\ \text{old}})}{(V_{base,\ \text{new}} / V_{base,\ \text{old}})^2} $$

  • Example: For multiple generators on a common bus, convert all reactances to a common system base before drawing the reactance diagram.

II. PROTECTIVE RELAYS: OPERATING PRINCIPLES & CHARACTERISTICS

Fundamental Relay Concepts

  • Operating Principle:

    • Electromagnetic Attraction: plunger or armature attracted by magnetic force (DC/AC).

    • Electromagnetic Induction: Rotating magnetic field induces torque in a disc or cup (AC only).

  • Characteristics:

    • Definite Time (DT): Fixed time delay after pickup.

    • Inverse Definite Minimum Time (IDMT): Operating time inversely proportional to fault current magnitude. Has a minimum time (dial setting).

  • Key Terms:

    • Pick-up Value: Minimum current/voltage to operate relay.

    • Time Dial Setting (TMS): Multiplier for the basic time curve.

    • Plug Setting Multiplier (PSM): $$\displaystyle \text{PSM} = \frac{\text{Fault Current}}{\text{Relay Pick-up Current}} $$

IDMT Relay Operation Time Calculation

Standard IEC/BS curves: Standard Inverse (SI), Very Inverse (VI), Extremely Inverse (EI).

  • Formula (for Standard Inverse Curve):

$$ t = \frac{0.14 \times \text{TMS}}{(\text{PSM})^{0.02} - 1} \ \text{seconds} \boxed{} $$

(Note: Exponent varies with curve type).

  • Steps:

    1. Find relay primary pick-up current from CT ratio & relay setting.

    2. Calculate PSM = Fault current / Relay pick-up current.

    3. Apply formula with given TMS.

Electromechanical Relays

  • Induction Disc Relay:

    • Construction: Electromagnet, aluminum disc, spring, coil, gear.

    • Principle: Two out-of-phase fluxes (from split poles) induce eddy currents in disc, producing torque.

$$ T \propto \phi_1 \phi_2 \sin \delta $$

*   **Application:** Overcurrent, directional, distance, reverse power.

*   **Minimize Overrun (disc inertia):** Use **braking magnet** (permanent magnet) to provide braking torque near operation point.
  • Induction Cup Relay:

    • Construction: Stationary electromagnets, cylindrical cup (conducting), rotor with control spring.

    • Principle: Similar to disc, but cup has lower inertia → faster operation, higher sensitivity.

    • Reset to Pick-up Ratio: Typically > 0.9 (very close to 1), meaning it resets at a current very near the pickup value. Better than disc relay.

Static Relays (Electronic Relays)

  • Advantages: No moving parts → faster, more accurate, adjustable characteristics, multi-function, self-test.

  • Functional Building Blocks:

    • Level Detector: Outputs 1 if input > set value, else 0.

    • Comparator: Compares two inputs (amplitude or phase).

      • Amplitude Comparator: $$\displaystyle |A| > |B| $$?

      • Phase Comparator: $$\displaystyle \angle(A) - \angle(B) > \theta $$?

    • Logic Circuits: AND, OR, NOT for combining comparator outputs.

  • Conversion:

    • Amplitude to Phase: Use a time delay on one input. $A \sin \omega t$ vs $A \sin (\omega t + \phi)$ after delay becomes phase comparison.

    • Phase to Amplitude: Use a phase-shifting network (RC) to convert phase difference into amplitude difference.

  • Specific Relays:

    • Static Directional Relay: Uses phase comparator. Compares fault current ($I$) and reference voltage ($V$). Operates if $\angle(V) - \angle(I)$ is within set directional window (e.g., $$\displaystyle -90^\circ $$ to $$\displaystyle +90^\circ $$).

    • Static Distance Relay: Measures impedance $$\displaystyle Z = V/I $$. Uses amplitude comparator (circle characteristic) or phase comparator (quadrilateral).

Microprocessor/Numerical Relays

  • Block Diagram:

    CT/VT → Analog Input → Anti-aliasing Filter → **ADC** → **CPU/Microprocessor** (runs protection algorithm) → Memory (settings, data) → Output Logic → Trip Signal

  • Software Development: Implements complex algorithms (Fourier for phasors, distance impedance calculation, differential restraint). Enables self-monitoring, communication (IEC 61850), and multiple functions in one unit.

  • Logic Circuits: Provide security (blocking signals, timers) and dependability (multiple criteria must be met).

Relay Characteristics on R-X Diagram

  • Impedance Relay (Plain):

    • Characteristic: Circle with center at origin. $$\displaystyle |Z| < Z_{set} $$ → Trip.

    • Operation: Measures impedance. Trips for faults within the circle.

    • Application: Simple distance protection, but non-directional.

  • MHO Relay (Admittance/Offset Impedance):

    • Characteristic: Circle passing through origin. Diameter along the line $$\displaystyle Z = Z_{set} e^{j(\theta - 90^\circ)} $$.

    • Directional: Only operates for faults in the forward direction (inside the circle and in direction of line).

    • Application: Primary protection for long transmission lines (Zone 1). Resists power swings (swing impedance locus is a line through origin, may not enter MHO circle).

  • OFF-SET MHO Relay:

    • Characteristic: MHO circle offset from origin towards the resistive axis.

    • Need: To cover high-resistance faults (large R component) that a plain MHO might miss. Used for Zone 2/3 settings.


III. CIRCUIT BREAKERS: THEORY, TYPES & SELECTION

Arc Phenomenon & Interruption Theory

  • Arc Formation: When contacts separate, ionization of air/gas creates a low-resistance path → high current arc.

  • Theory of Current Interruption (Energy Balance):

    • At current zero (AC), arc attempts to extinguish.

    • Restriking Voltage ($$\displaystyle v_r $$): Transient voltage across contacts immediately after current zero. High $di/dt$ → high $dv/dt$ → may restrike.

    • Recovery Voltage ($$\displaystyle v_{rec} $$): Sustained power frequency voltage across contacts after arc extinction. Must withstand this.

    • Condition for Successful Interruption: Dielectric strength of arc space must build up faster than restriking voltage rise.

  • Methods to Increase Dielectric Strength: Rapid cooling (SF6, Vacuum), lengthening arc (oil, air blast), deionization.

Arc Quenching Media & Methods

  • Methods:

    1. High Resistance Method: Increase arc resistance (air blast, SF6 puffer).

    2. Low Resistance (Zero-Current) Method: Use medium where arc extinguishes naturally at current zero (vacuum, SF6 thermal blast).

    3. Oil Decomposition: Gas bubbles from oil decomposition provide cooling and insulation (oil CB).

Types of Circuit Breakers

Feature Oil Circuit Breaker (OCB) Air Blast CB (ABCB) SF₆ CB Vacuum CB (VCB)
Principle Arc in oil → gas bubbles provide insulation & cooling. High-pressure air blast extinguishes arc. SF₆ gas has high dielectric strength & electronegativity. Arc in vacuum → no medium to ionize, extinguishes at current zero.
Types Bulk Oil: Oil acts as insulation & quenching. <br> Minimum Oil: Oil only for quenching, less oil. Axial: Air flows along arc path. <br> Cross-air: Air flows across contacts. <br> Radial: Air flows radially. Puffer: Piston compresses SF₆ during operation. <br> Thermal Blast: Uses arc heat to create gas flow. Single-pause, magnetic field for arc control.
Advantages Simple, cheap for low voltage. Fast operation, no fire risk, good for EHV. Excellent dielectric, quiet, low maintenance, self-healing. Very fast, long life, no maintenance, compact, no gas handling.
Disadvantages Fire risk, oil maintenance, pollution. Current chopping → overvoltages. Need compressor. Gas leakage, moisture sensitivity, expensive. Limited breaking capacity (~40 kA), not for very high MVA.
Application Up to 33 kV (bulk), 245 kV (min oil). 132 kV to 400 kV. 72.5 kV to 800 kV (recommended range). Up to 38 kV (typical), up to 72.5 kV. Recommended for distribution & sub-transmission.
Comparison Bulk vs Min Oil: Min oil uses less oil, smaller tank, but higher thermal stress on oil. Current Chopping: Occurs when arc is forced to extinguish before natural current zero (in small currents). Axial type most susceptible; Cross-air least affected. SF₆ vs Others: Superior dielectric strength (3x air), arc-quenching, quiet, low maintenance. Replaces oil & air blast for EHV.

Circuit Breaker Ratings & Selection

  • Breaking Capacity: Maximum RMS current (kA) it can interrupt at specified recovery voltage. Most important rating. Based on symmetrical RMS current.

  • Making Capacity: Maximum peak current (kA) it can close onto a fault. Making Capacity = √2 × Breaking Capacity × (1 + X/R factor). Usually higher than breaking capacity.

  • Selection Factors:

    1. Voltage Rating (system voltage).

    2. Breaking Capacity (≥ maximum 3-phase fault current at point).

    3. Making Capacity.

    4. Type of System (grounded/ungrounded).

    5. Duty Cycle (number of operations, CO, OCO).

    6. Installation Conditions (indoor/outdoor, altitude).

  • Importance of Testing: To verify ratings (short-circuit, mechanical, dielectric). Types: Type Test (design), Routine Test (each unit), Commissioning Test.


IV. APPLICATION-SPECIFIC PROTECTION SCHEMES

Generator/Alternator Protection

  • Common Faults:

    • Stator: Phase-to-phase, phase-to-ground (winding faults).

    • Rotor: Field winding faults (ground, turn-to-turn), loss of excitation.

    • External: Back-up protection for system faults.

  • Stator Protection (Percentage Differential - Merz-Price):

    • Principle: Compare currents entering/leaving stator winding via CTs. Under normal/through fault, currents balance. Internal fault → unbalance → relay operates.

    • Slope: Characteristic has a slope (e.g., 15-30%) to allow for CT mismatch & magnetizing current during external faults. Stability during through faults is key.

    • CT Ratio Calculation: Ensure $$\displaystyle I_{CT,\ HV} \times \text{CT ratio}_{HV} = I_{CT,\ LV} \times \text{CT ratio}_{LV} $$ for balanced 3-phase.

  • Rotor Protection:

    • Loss of Excitation: Detects transition from inductive to capacitive power factor (impedance relay in $R-X$ plane).

    • Field Failure: Uses reverse power relay or offset MHO relay.

  • Generator-Transformer Unit Protection: Treats generator + transformer as one unit. Uses biased differential (high set for unit faults, low set for transformer inrush) or percentage differential with harmonic restraint.

  • Buchholz Relay (for Transformer/Unit): Gas-actuated relay in oil-filled tank. Operates for:

    • Minor Faults: Gas accumulation → alarm.

    • Major Faults: Oil surge → trip.

Transformer Protection

  • Internal Faults: Winding shorts, inter-turn faults.

  • External Faults: Back-up overcurrent.

  • Differential Protection (Merz-Price):

    • Challenge: Star-Delta connection introduces 30° phase shift between HV & LV currents.

    • CT Ratio Calculation: To compensate, CT ratios must be chosen such that:

$$ \frac{I_{HV}}{I_{LV}} = \frac{\text{CT Ratio}_{LV}}{\text{CT Ratio}_{HV}} = \frac{V_{LV}}{V_{HV}} \times \frac{\sqrt{3}}{1} \ \text{(for Star-Delta)} \boxed{} $$

    (For Star-Star, ratio = $$\displaystyle V_{LV}/V_{HV} $$).

*   **Procedure:** Calculate secondary currents for both sides under balanced load. Set CT ratios to make them equal.
  • Other Protections:

    • Overcurrent: Back-up.

    • Restricted Earth Fault (REF): Sensitive protection for earth faults near neutral (only senses faults within transformer zone).

    • Buchholz Relay: For oil-filled transformers.

    • Temperature Monitoring: Winding temperature, oil temperature.

Busbar Protection

  • Importance: Busbar fault → massive outage, loss of multiple circuits.

  • Differential Protection Scheme:

    • CTs on all incoming/outgoing circuits.

    • Sum of CT currents should be zero under normal condition.

    • Internal fault → sum ≠ 0 → relay operates.

    • Challenge: CT saturation during external faults can cause false operation.

  • Frame Leakage Protection Scheme:

    • CTs on busbar frame/ground only.

    • Under normal, no current in frame CT.

    • Internal fault → fault current flows through frame → frame CT operates.

    • Simple, but not fail-safe (if frame insulation fails).

  • Other Methods:

    • High-Impedance Differential: Uses high series impedance to prevent maloperation during CT saturation.

    • Biased Differential: Similar to transformer differential, with slope to handle through faults.

Transmission Line Protection

  • Pilot Relaying Schemes: Use communication channel (pilot) between line ends for fast, selective tripping.

    • Types of Pilots:

      • Pilot Wires: Dedicated copper pairs. Reliable, fast, but expensive for long distances.

      • Power Line Carrier (PLCP): Uses transmission line itself as channel. Frequency: 30-500 kHz. Merits: No extra wires. Demerits: Attenuation, noise, requires coupling capacitors & line traps. Used for 33 kV to 220 kV.

      • Microwave: Point-to-point radio. Fast, reliable, independent of line. Used for EHV (400 kV+).

    • Phase Comparison Scheme (Carrier):

      • Compares phase of currents at both ends.

      • Operation: For internal fault, currents at both ends are in phase (both flow towards fault). Carrier signal sent → tripping. For external fault, currents out of phase → blocking.

      • Sketch: Shows CTs, phase comparator at each end, carrier transmitter/receiver, blocking/tripping logic.

  • Distance Protection:

    • Measures impedance $$\displaystyle Z = V/I $$ to fault.

    • MHO Relay is primary for Zone 1 (80-90% line length). OFF-SET MHO for Zones 2 & 3 (reach beyond line, with offset for high-resistance faults).

    • Protection Zones:

      • Zone 1: 80-90% of line. Instantaneous.

      • Zone 2: Covers remaining line + backup for next line (120-150% of line). Time delay (e.g., 0.5 s).

      • Zone 3: Backup for remote lines, and as last resort. Long reach, long delay (e.g., 1.0 s).

Current Limiting Reactors

  • Types: Air-core (dry, no saturation) and Iron-core (saturates at high current).

  • Construction: Series reactor installed in each feeder or at busbars.

  • Application: Limit fault current magnitude during short circuits. Protect equipment (breakers, cables) from high thermal/mechanical stress. Used in generator neutral, bus-section, and feeder applications.

  • Role: Increases system impedance, thereby reducing $$\displaystyle I_{fault} = E / (Z_{sys} + Z_{reactor}) $$.


V. AUXILIARY & OTHER PROTECTION DEVICES

High Rupturing Capacity (HRC Fuses)

  • Function: Fast, high-current interrupting device for LT switchgear.

  • Principle: Fusible element melts under overcurrent. Sand/quenching material surrounds element to cool arc and prevent restrike.

  • Application: Transformer protection (LT side), motor protection, capacitor banks.

Current Transformers (CTs) & Voltage Transformers (VTs)

  • CT Ratio Selection for Differential Protection:

    • Goal: Make CT secondary currents equal under normal load.

    • For Star-Delta Transformer:

      • HV side (Star): $$\displaystyle I_{HV, ph} = \frac{S}{\sqrt{3} V_{HV}} $$

      • LV side (Delta): $$\displaystyle I_{LV, line} = \frac{S}{\sqrt{3} V_{LV}} $$, $$\displaystyle I_{LV, ph} = I_{LV, line} / \sqrt{3} $$

      • Therefore, $$\displaystyle \frac{I_{HV, ph}}{I_{LV, ph}} = \frac{V_{LV}}{V_{HV}} \times \sqrt{3} $$

      • CT ratios must satisfy: $$\displaystyle \frac{\text{CT Ratio}_{HV}}{\text{CT Ratio}_{LV}} = \frac{V_{LV}}{V_{HV}} \times \sqrt{3} $$

  • CT Saturation: Occurs when primary current is so high that core flux exceeds saturation limit. Effect: CT secondary current is distorted (flattened) and inaccurate. Can cause failure of differential protection (through fault) or false operation (internal fault). Use Class X/TP CTs for protection.

Buchholz Relay (Detailed)

  • Location: Installed in the pipe between transformer tank and conservator.

  • Working Principle:

    1. Gas Accumulation (Alarm): Minor internal faults generate gas. Gas collects in relay chamber → float drops → closes alarm contact.

    2. Oil Surge (Trip): Major fault generates large volume of gas rapidly → oil surges towards conservator → deflects baffle plate → closes trip contact.

  • Protects: Against internal faults with oil decomposition (winding shorts, core faults). Does not protect against external faults or minor insulation deterioration without gas.


VI. SYSTEM & MODERN PROTECTION CONCEPTS

Security and Reliability

  • Reliability (Dependability): Relay must operate when required (for faults in its zone). False trips are unacceptable.

  • Security: Relay must not operate when not required (for faults outside zone or no fault). Failure to trip is unacceptable.

  • How Ensured:

    • Redundancy: Dual protection schemes (e.g., two independent differential relays).

    • Diversity: Different operating principles (e.g., differential + overcurrent).

    • Proper Setting & Coordination: Ensure selectivity.

    • Testing & Maintenance: Regular functional tests.

    • Logic in Numerical Relays: Blocking signals, timers, harmonic restraint (for transformer inrush).

Microprocessor-Based Protection Schemes

  • Advantages over Conventional:

    • Multiple functions in one unit (OC, distance, differential, autoreclose).

    • Adaptive settings (change with system conditions).

    • Self-monitoring & diagnostics.

    • Communication (SCADA, IEC 61850) for data, control, and event recording.

    • Advanced algorithms (Fourier, traveling wave).

    • Lower burden on CTs/VTs.

    • No drift (digital).

  • Implementation: Software executes protection logic. Hardware: ADC, DSP/CPU, memory, I/O, communication port.

Software Development for Protection

  • Role in Security & Reliability:

    • Secure Code: Prevents bugs causing false trips.

    • Verification & Validation (V&V): Extensive testing (simulation, hardware-in-loop).

    • Setting Management: Secure storage, easy retrieval, version control.

    • Fail-Safe Design: Watchdog timers, default safe states.

    • Cyber Security: Authentication, encryption for communication.


VII. CALCULATION & DESIGN PROBLEMS (INTEGRATED)

1. CT Ratio Calculation for Transformer Differential (Star-Delta)

Problem: 3-phase transformer 0.4 kV (Star) / 11 kV (Delta). CT ratio on LV side = 500/5. Find CT ratio on HV side.

  • Step 1: $$\displaystyle V_{LV} = 0.4 \ \text{kV} $$ (phase), $$\displaystyle V_{HV} = 11 \ \text{kV} $$ (line). For Star-Delta, $$\displaystyle V_{HV, ph} = 11 \ \text{kV} $$.

  • Step 2: Current ratio (line) $$\displaystyle I_{LV} / I_{HV} = 11 / 0.4 = 27.5 $$.

  • Step 3: CT secondary current should be equal. So, $$\displaystyle I_{HV, ph} \times \text{CT Ratio}_{HV} = I_{LV, line} \times \text{CT Ratio}_{LV} $$.

  • Step 4: But $$\displaystyle I_{HV, ph} = I_{HV, line} / \sqrt{3} $$. So:

$$ \frac{I_{HV, line}}{\sqrt{3}} \times \text{CT Ratio}_{HV} = I_{LV, line} \times 500/5 $$

$$ \Rightarrow \text{CT Ratio}_{HV} = \sqrt{3} \times \frac{I_{LV, line}}{I_{HV, line}} \times \frac{500}{5} = \sqrt{3} \times 27.5 \times 100 = 4762.5 $$

  • Answer: $$\displaystyle \boxed{4762.5/5 \ \text{A} \ \text{or standard} \ 5000/5 \ \text{A}} $$

2. Fault Current Calculation for Unloaded Alternator

Problem: 25 MVA, 13.2 kV, solidly grounded. $$\displaystyle X_d'' = 0.25 $$ p.u., $$\displaystyle X_2 = 0.35 $$ p.u., $$\displaystyle X_0 = 0.1 $$ p.u. SLG fault at terminals. Find $$\displaystyle I_f $$ and line-to-line voltage.

  • Step 1: $$\displaystyle E_f = 1.0 $$ p.u. (reference). $$\displaystyle Z_1 = j0.25 $$, $$\displaystyle Z_2 = j0.35 $$, $$\displaystyle Z_0 = j0.1 $$.

  • Step 2: SLG fault: $$\displaystyle I_1 = I_2 = I_0 = \frac{1.0}{j(0.25+0.35+0.1)} = \frac{1}{j0.7} = -j1.4286 $$ p.u.

  • Step 3: Fault current: $$\displaystyle I_f = 3I_0 = 3 \times 1.4286 = 4.2857 $$ p.u.

  • Step 4: Convert to actual: Base current $$\displaystyle I_{base} = \frac{25 \times 10^6}{\sqrt{3} \times 13.2 \times 10^3} = 1092.4 \ \text{A} $$. $$\displaystyle I_f = 4.2857 \times 1092.4 = 4682 \ \text{A} $$.

  • Step 5: Line-to-line voltage (e.g., $$\displaystyle V_{bc} $$) during SLG fault (A-G):

$$ V_{bc} = V_{b0} + V_{b1} + V_{b2} $$

$$ V_1 = E_f - I_1 Z_1 = 1 - (-j1.4286 \times j0.25) = 1 - 0.3571 = 0.6429 \ \text{p.u.} $$

$$ V_2 = -I_2 Z_2 = -(-j1.4286 \times j0.35) = -0.5 \ \text{p.u.} $$

$$ V_0 = -I_0 Z_0 = -(-j1.4286 \times j0.1) = -0.1429 \ \text{p.u.} $$

For phase B: $$\displaystyle V_{b1} = a^2 V_1 $$, $$\displaystyle V_{b2} = a V_2 $$, $$\displaystyle V_{b0} = V_0 $$.

$$ V_{bc} = (V_{b1} - V_{c1}) + (V_{b2} - V_{c2}) + (V_{b0} - V_{c0}) $$

Since $$\displaystyle V_0 $$ is zero-sequence, $$\displaystyle V_{b0} - V_{c0} = 0 $$.

$$ V_{bc} = V_1(a^2 - a) + V_2(a - a^2) = (V_1 - V_2) j\sqrt{3} $$

$$ V_{bc} = (0.6429 - (-0.5)) j\sqrt{3} = 1.1429 \times j1.732 = j1.98 \ \text{p.u.} $$

Magnitude = **1.98 p.u.** (Line-to-line voltage rises during SLG fault!).

3. IDMT Relay Operation Time

Problem: 5 A, 2.2 s IDMT relay, plug setting 125%, TMS=0.6. CT 400/5. Fault current = 4000 A.

  • Step 1: Relay primary pick-up = $$\displaystyle 5 \ \text{A} \times 1.25 = 6.25 \ \text{A} $$.

  • Step 2: Fault current seen by relay = CT secondary current = $$\displaystyle 4000 \times (5/400) = 50 \ \text{A} $$.

  • Step 3: PSM = Fault current / Relay pick-up = $$\displaystyle 50 / 6.25 = 8 $$.

  • Step 4: For Standard Inverse (SI) curve: $$\displaystyle t = \frac{0.14 \times \text{TMS}}{(\text{PSM})^{0.02} - 1} = \frac{0.14 \times 0.6}{8^{0.02} - 1} $$.

    $$\displaystyle 8^{0.02} = e^{0.02 \ln 8} = e^{0.02 \times 2.079} = e^{0.04158} = 1.0424 $$.

    $$\displaystyle t = \frac{0.084}{0.0424} = 1.98 \ \text{s} $$.

  • Answer: $\boxed{t \approx 1.98 \ \text{seconds}}$

4. Percentage Differential Relay Stability Check

Problem: Stator protection, 15% slope. Fault: $$\displaystyle I_{CT1} = 400 \ \text{A} $$, $$\displaystyle I_{CT2} = 320 \ \text{A} $$. CT ratio = 500/5. Will relay trip?

  • Step 1: Bias/Through Current $$\displaystyle I_{through} = \frac{I_{CT1} + I_{CT2}}{2} = \frac{400+320}{2} = 360 \ \text{A} $$.

  • Step 2: Operating Current $$\displaystyle I_{op} = |I_{CT1} - I_{CT2}| = |400 - 320| = 80 \ \text{A} $$.

  • Step 3: Slope Setting: 15% means relay operates if $$\displaystyle I_{op} > 0.15 \times I_{through} $$.

    $$\displaystyle 0.15 \times 360 = 54 \ \text{A} $$.

  • Step 4: Since $$\displaystyle I_{op} (80 \ \text{A}) > 54 \ \text{A} $$, relay will trip.

  • Note: CT ratio is same on both sides, so actual primary currents are proportional. Check is valid on secondary currents.

5. Per-Unit Reactance Conversion

Problem: Three generators on common bus. Convert to base: 200 MVA, 35 kV.

*   G1: 100 MVA, 33 kV, 10%

*   G2: 150 MVA, 32 kV, 8%

*   G3: 110 MVA, 30 kV, 12%
  • Step 1: For each generator, calculate its own base current: $$\displaystyle I_{base,G} = S_{base,G} / (\sqrt{3} V_{base,G}) $$.

  • Step 2: Convert each reactance to new base using formula:

$$ X_{\text{new}} = X_{\text{old}} \times \frac{S_{base,\ \text{new}}}{S_{base,\ \text{old}}} \times \left( \frac{V_{base,\ \text{old}}}{V_{base,\ \text{new}}} \right)^2 $$

  • Calculations:

    • G1: $$\displaystyle X_1 = 0.10 \times \frac{200}{100} \times \left( \frac{33}{35} \right)^2 = 0.10 \times 2 \times 0.888 = 0.1776 $$ p.u.

    • G2: $$\displaystyle X_2 = 0.08 \times \frac{200}{150} \times \left( \frac{32}{35} \right)^2 = 0.08 \times 1.333 \times 0.836 = 0.0892 $$ p.u.

    • G3: $$\displaystyle X_3 = 0.12 \times \frac{200}{110} \times \left( \frac{30}{35} \right)^2 = 0.12 \times 1.818 \times 0.7347 = 0.160 $$ p.u.

  • Result: Reactance diagram: Three generators in parallel at common bus (35 kV), with $$\displaystyle X_1=0.1776 $$, $$\displaystyle X_2=0.0892 $$, $$\displaystyle X_3=0.160 $$ p.u. on 200 MVA, 35 kV base.


[!TIP]

Exam Focus: Be prepared to derive fault current expressions (especially DLG), calculate CT ratios for transformer differentials (Star-Delta is a favorite), compute IDMT times (memorize SI curve formula), and draw sequence networks for all fault types. For circuit breakers, compare SF6, VCB, and OCB. Always box final formulas and numerical answers.

Go to where you left off?

Quick Add to Notes

Save questions, your own notes and screenshots into notes filed by unit. It takes a free account.

Create free account

Have an account? Log in