UNIT 4: POWER SYSTEM PROTECTION - EXAM-FOCUSED SHORT NOTES
I. FAULT ANALYSIS & SYMMETRICAL COMPONENTS
Types of Power System Faults
-
Symmetrical Fault: Three-phase fault (LLLG). All phases affected equally. System remains balanced. Highest fault current.
-
Unsymmetrical Faults:
-
Single Line-to-Ground (SLG/LG): Most common (~70%).
-
Line-to-Line (LL): Second most common.
-
Double Line-to-Ground (DLG/LLG):
-
-
Fault Level / Fault MVA: The maximum power (in MVA) that can flow into a fault at a given point. It determines the required breaking capacity of circuit breakers.
$$ \text{Fault MVA} = \sqrt{3} \times V_{\text{base}} \times I_{\text{fault}} $$
Symmetrical Components (Krenz's Theorem)
-
Significance: Any set of three unbalanced phasors (voltages/currents) can be resolved into three sets of balanced phasors:
-
Positive Sequence ($$\displaystyle V_1, I_1 $$): Balanced, phase sequence A-B-C.
-
Negative Sequence ($$\displaystyle V_2, I_2 $$): Balanced, phase sequence A-C-B.
-
Zero Sequence ($$\displaystyle V_0, I_0 $$): All three phasors in phase.
-
-
Simplification: Allows analysis of complex unsymmetrical faults by solving three simple, independent, balanced systems.
Sequence Networks
-
Positive Sequence Network: Represents the normal balanced system. Contains internal EMFs ($$\displaystyle E_f $$). Reactance = $$\displaystyle X_d'' $$ (sub-transient) for generators during faults.
-
Negative Sequence Network: No internal EMFs ($$\displaystyle E_2 = 0 $$). Reactance = $$\displaystyle X_d'' $$ (for synchronous machines, often same as positive sequence for faults).
-
Zero Sequence Network: Path depends on grounding. For a generator with solidly grounded neutral, $$\displaystyle Z_0 = Z_{g} + 3Z_n $$ (where $$\displaystyle Z_g $$ is generator zero seq. reactance, $$\displaystyle Z_n $$ is neutral grounding impedance). No zero sequence current flows if neutral is isolated.
Fault Current Derivation (at Generator Terminals, Unloaded, Solid Ground)
General Method: Interconnect sequence networks based on fault type. Solve for $$\displaystyle I_0, I_1, I_2 $$. Fault currents are derived from these.
-
Single Line-to-Ground (SLG) Fault (Phase A to Ground):
-
Connection: Series: $$\displaystyle Z_1 + Z_2 + Z_0 $$.
-
Sequence Current:
-
$$ I_1 = I_2 = I_0 = \frac{E_f}{Z_1 + Z_2 + Z_0} $$
* **Fault Current (Phase A):**
$$ I_f = I_a = 3I_0 = \frac{3E_f}{Z_1 + Z_2 + Z_0} \boxed{} $$
-
Line-to-Line (LL) Fault (Phase B & C):
-
Connection: Parallel: $$\displaystyle I_1 = -I_2 $$, $$\displaystyle I_0 = 0 $$. Networks in parallel: $$\displaystyle Z_1 + Z_2 $$.
-
Sequence Current:
-
$$ I_1 = -I_2 = \frac{E_f}{Z_1 + Z_2} $$
* **Fault Current (e.g., $$\displaystyle I_b $$):**
$$ I_f = I_b = \sqrt{3} I_1 \angle 30^\circ \boxed{} $$
-
Double Line-to-Ground (DLG) Fault (Phases B & C to Ground):
-
Connection: $$\displaystyle I_1 + I_2 + I_0 = 0 $$. Networks in parallel: $$\displaystyle Z_1 \parallel (Z_2 + Z_0) $$.
-
Sequence Currents:
-
$$ I_1 = \frac{E_f}{Z_1 + \frac{Z_2 Z_0}{Z_2 + Z_0}} $$
$$ I_2 = -I_1 \frac{Z_0}{Z_2 + Z_0}, \quad I_0 = -I_1 \frac{Z_2}{Z_2 + Z_0} $$
* **Fault Current (Phase A):**
$$ I_a = 0, \quad I_b = I_1 (\sqrt{3} \angle 30^\circ - \frac{Z_2}{Z_2+Z_0}), \quad I_c = I_1 (\sqrt{3} \angle -30^\circ - \frac{Z_0}{Z_2+Z_0}) $$
-
Three-Phase Fault (LLLG):
-
Connection: Only positive sequence network. $$\displaystyle I_1 = E_f / Z_1 $$, $$\displaystyle I_2 = I_0 = 0 $$.
-
Fault Current:
-
$$ I_f = I_a = I_1 = \frac{E_f}{Z_1} \boxed{} $$
Effect of Fault Impedance ($$\displaystyle Z_f $$)
-
Adds to the impedance in the fault path.
-
SLG Fault: $$\displaystyle I_f = \frac{3E_f}{Z_1 + Z_2 + Z_0 + 3Z_f} $$
-
LL Fault: $$\displaystyle I_f = \frac{\sqrt{3} E_f}{Z_1 + Z_2 + Z_f} $$
-
DLG Fault: $$\displaystyle Z_f $$ appears in parallel with $$\displaystyle Z_0 $$ in the negative-zero sequence loop.
-
Result: Fault current decreases as $$\displaystyle Z_f $$ increases.
System Representation for Fault Studies
-
Per-Unit System: Simplifies calculations by eliminating voltage/transformer ratio conversions.
-
Base Quantity Selection: Choose common $$\displaystyle S_{base} $$ and $$\displaystyle V_{base} $$ for the entire system.
-
Conversion of Reactances:
$$ X_{\text{p.u., new}} = X_{\text{p.u., old}} \times \frac{(S_{base,\ \text{new}} / S_{base,\ \text{old}})}{(V_{base,\ \text{new}} / V_{base,\ \text{old}})^2} $$
- Example: For multiple generators on a common bus, convert all reactances to a common system base before drawing the reactance diagram.
II. PROTECTIVE RELAYS: OPERATING PRINCIPLES & CHARACTERISTICS
Fundamental Relay Concepts
-
Operating Principle:
-
Electromagnetic Attraction: plunger or armature attracted by magnetic force (DC/AC).
-
Electromagnetic Induction: Rotating magnetic field induces torque in a disc or cup (AC only).
-
-
Characteristics:
-
Definite Time (DT): Fixed time delay after pickup.
-
Inverse Definite Minimum Time (IDMT): Operating time inversely proportional to fault current magnitude. Has a minimum time (dial setting).
-
-
Key Terms:
-
Pick-up Value: Minimum current/voltage to operate relay.
-
Time Dial Setting (TMS): Multiplier for the basic time curve.
-
Plug Setting Multiplier (PSM): $$\displaystyle \text{PSM} = \frac{\text{Fault Current}}{\text{Relay Pick-up Current}} $$
-
IDMT Relay Operation Time Calculation
Standard IEC/BS curves: Standard Inverse (SI), Very Inverse (VI), Extremely Inverse (EI).
- Formula (for Standard Inverse Curve):
$$ t = \frac{0.14 \times \text{TMS}}{(\text{PSM})^{0.02} - 1} \ \text{seconds} \boxed{} $$
(Note: Exponent varies with curve type).
-
Steps:
-
Find relay primary pick-up current from CT ratio & relay setting.
-
Calculate PSM = Fault current / Relay pick-up current.
-
Apply formula with given TMS.
-
Electromechanical Relays
-
Induction Disc Relay:
-
Construction: Electromagnet, aluminum disc, spring, coil, gear.
-
Principle: Two out-of-phase fluxes (from split poles) induce eddy currents in disc, producing torque.
-
$$ T \propto \phi_1 \phi_2 \sin \delta $$
* **Application:** Overcurrent, directional, distance, reverse power.
* **Minimize Overrun (disc inertia):** Use **braking magnet** (permanent magnet) to provide braking torque near operation point.
-
Induction Cup Relay:
-
Construction: Stationary electromagnets, cylindrical cup (conducting), rotor with control spring.
-
Principle: Similar to disc, but cup has lower inertia → faster operation, higher sensitivity.
-
Reset to Pick-up Ratio: Typically > 0.9 (very close to 1), meaning it resets at a current very near the pickup value. Better than disc relay.
-
Static Relays (Electronic Relays)
-
Advantages: No moving parts → faster, more accurate, adjustable characteristics, multi-function, self-test.
-
Functional Building Blocks:
-
Level Detector: Outputs 1 if input > set value, else 0.
-
Comparator: Compares two inputs (amplitude or phase).
-
Amplitude Comparator: $$\displaystyle |A| > |B| $$?
-
Phase Comparator: $$\displaystyle \angle(A) - \angle(B) > \theta $$?
-
-
Logic Circuits: AND, OR, NOT for combining comparator outputs.
-
-
Conversion:
-
Amplitude to Phase: Use a time delay on one input. $A \sin \omega t$ vs $A \sin (\omega t + \phi)$ after delay becomes phase comparison.
-
Phase to Amplitude: Use a phase-shifting network (RC) to convert phase difference into amplitude difference.
-
-
Specific Relays:
-
Static Directional Relay: Uses phase comparator. Compares fault current ($I$) and reference voltage ($V$). Operates if $\angle(V) - \angle(I)$ is within set directional window (e.g., $$\displaystyle -90^\circ $$ to $$\displaystyle +90^\circ $$).
-
Static Distance Relay: Measures impedance $$\displaystyle Z = V/I $$. Uses amplitude comparator (circle characteristic) or phase comparator (quadrilateral).
-
Microprocessor/Numerical Relays
-
Block Diagram:
CT/VT → Analog Input → Anti-aliasing Filter → **ADC** → **CPU/Microprocessor** (runs protection algorithm) → Memory (settings, data) → Output Logic → Trip Signal -
Software Development: Implements complex algorithms (Fourier for phasors, distance impedance calculation, differential restraint). Enables self-monitoring, communication (IEC 61850), and multiple functions in one unit.
-
Logic Circuits: Provide security (blocking signals, timers) and dependability (multiple criteria must be met).
Relay Characteristics on R-X Diagram
-
Impedance Relay (Plain):
-
Characteristic: Circle with center at origin. $$\displaystyle |Z| < Z_{set} $$ → Trip.
-
Operation: Measures impedance. Trips for faults within the circle.
-
Application: Simple distance protection, but non-directional.
-
-
MHO Relay (Admittance/Offset Impedance):
-
Characteristic: Circle passing through origin. Diameter along the line $$\displaystyle Z = Z_{set} e^{j(\theta - 90^\circ)} $$.
-
Directional: Only operates for faults in the forward direction (inside the circle and in direction of line).
-
Application: Primary protection for long transmission lines (Zone 1). Resists power swings (swing impedance locus is a line through origin, may not enter MHO circle).
-
-
OFF-SET MHO Relay:
-
Characteristic: MHO circle offset from origin towards the resistive axis.
-
Need: To cover high-resistance faults (large R component) that a plain MHO might miss. Used for Zone 2/3 settings.
-
III. CIRCUIT BREAKERS: THEORY, TYPES & SELECTION
Arc Phenomenon & Interruption Theory
-
Arc Formation: When contacts separate, ionization of air/gas creates a low-resistance path → high current arc.
-
Theory of Current Interruption (Energy Balance):
-
At current zero (AC), arc attempts to extinguish.
-
Restriking Voltage ($$\displaystyle v_r $$): Transient voltage across contacts immediately after current zero. High $di/dt$ → high $dv/dt$ → may restrike.
-
Recovery Voltage ($$\displaystyle v_{rec} $$): Sustained power frequency voltage across contacts after arc extinction. Must withstand this.
-
Condition for Successful Interruption: Dielectric strength of arc space must build up faster than restriking voltage rise.
-
-
Methods to Increase Dielectric Strength: Rapid cooling (SF6, Vacuum), lengthening arc (oil, air blast), deionization.
Arc Quenching Media & Methods
-
Methods:
-
High Resistance Method: Increase arc resistance (air blast, SF6 puffer).
-
Low Resistance (Zero-Current) Method: Use medium where arc extinguishes naturally at current zero (vacuum, SF6 thermal blast).
-
Oil Decomposition: Gas bubbles from oil decomposition provide cooling and insulation (oil CB).
-
Types of Circuit Breakers
| Feature | Oil Circuit Breaker (OCB) | Air Blast CB (ABCB) | SF₆ CB | Vacuum CB (VCB) |
|---|---|---|---|---|
| Principle | Arc in oil → gas bubbles provide insulation & cooling. | High-pressure air blast extinguishes arc. | SF₆ gas has high dielectric strength & electronegativity. | Arc in vacuum → no medium to ionize, extinguishes at current zero. |
| Types | Bulk Oil: Oil acts as insulation & quenching. <br> Minimum Oil: Oil only for quenching, less oil. | Axial: Air flows along arc path. <br> Cross-air: Air flows across contacts. <br> Radial: Air flows radially. | Puffer: Piston compresses SF₆ during operation. <br> Thermal Blast: Uses arc heat to create gas flow. | Single-pause, magnetic field for arc control. |
| Advantages | Simple, cheap for low voltage. | Fast operation, no fire risk, good for EHV. | Excellent dielectric, quiet, low maintenance, self-healing. | Very fast, long life, no maintenance, compact, no gas handling. |
| Disadvantages | Fire risk, oil maintenance, pollution. | Current chopping → overvoltages. Need compressor. | Gas leakage, moisture sensitivity, expensive. | Limited breaking capacity (~40 kA), not for very high MVA. |
| Application | Up to 33 kV (bulk), 245 kV (min oil). | 132 kV to 400 kV. | 72.5 kV to 800 kV (recommended range). | Up to 38 kV (typical), up to 72.5 kV. Recommended for distribution & sub-transmission. |
| Comparison | Bulk vs Min Oil: Min oil uses less oil, smaller tank, but higher thermal stress on oil. | Current Chopping: Occurs when arc is forced to extinguish before natural current zero (in small currents). Axial type most susceptible; Cross-air least affected. | SF₆ vs Others: Superior dielectric strength (3x air), arc-quenching, quiet, low maintenance. Replaces oil & air blast for EHV. |
Circuit Breaker Ratings & Selection
-
Breaking Capacity: Maximum RMS current (kA) it can interrupt at specified recovery voltage. Most important rating. Based on symmetrical RMS current.
-
Making Capacity: Maximum peak current (kA) it can close onto a fault. Making Capacity = √2 × Breaking Capacity × (1 + X/R factor). Usually higher than breaking capacity.
-
Selection Factors:
-
Voltage Rating (system voltage).
-
Breaking Capacity (≥ maximum 3-phase fault current at point).
-
Making Capacity.
-
Type of System (grounded/ungrounded).
-
Duty Cycle (number of operations, CO, OCO).
-
Installation Conditions (indoor/outdoor, altitude).
-
-
Importance of Testing: To verify ratings (short-circuit, mechanical, dielectric). Types: Type Test (design), Routine Test (each unit), Commissioning Test.
IV. APPLICATION-SPECIFIC PROTECTION SCHEMES
Generator/Alternator Protection
-
Common Faults:
-
Stator: Phase-to-phase, phase-to-ground (winding faults).
-
Rotor: Field winding faults (ground, turn-to-turn), loss of excitation.
-
External: Back-up protection for system faults.
-
-
Stator Protection (Percentage Differential - Merz-Price):
-
Principle: Compare currents entering/leaving stator winding via CTs. Under normal/through fault, currents balance. Internal fault → unbalance → relay operates.
-
Slope: Characteristic has a slope (e.g., 15-30%) to allow for CT mismatch & magnetizing current during external faults. Stability during through faults is key.
-
CT Ratio Calculation: Ensure $$\displaystyle I_{CT,\ HV} \times \text{CT ratio}_{HV} = I_{CT,\ LV} \times \text{CT ratio}_{LV} $$ for balanced 3-phase.
-
-
Rotor Protection:
-
Loss of Excitation: Detects transition from inductive to capacitive power factor (impedance relay in $R-X$ plane).
-
Field Failure: Uses reverse power relay or offset MHO relay.
-
-
Generator-Transformer Unit Protection: Treats generator + transformer as one unit. Uses biased differential (high set for unit faults, low set for transformer inrush) or percentage differential with harmonic restraint.
-
Buchholz Relay (for Transformer/Unit): Gas-actuated relay in oil-filled tank. Operates for:
-
Minor Faults: Gas accumulation → alarm.
-
Major Faults: Oil surge → trip.
-
Transformer Protection
-
Internal Faults: Winding shorts, inter-turn faults.
-
External Faults: Back-up overcurrent.
-
Differential Protection (Merz-Price):
-
Challenge: Star-Delta connection introduces 30° phase shift between HV & LV currents.
-
CT Ratio Calculation: To compensate, CT ratios must be chosen such that:
-
$$ \frac{I_{HV}}{I_{LV}} = \frac{\text{CT Ratio}_{LV}}{\text{CT Ratio}_{HV}} = \frac{V_{LV}}{V_{HV}} \times \frac{\sqrt{3}}{1} \ \text{(for Star-Delta)} \boxed{} $$
(For Star-Star, ratio = $$\displaystyle V_{LV}/V_{HV} $$).
* **Procedure:** Calculate secondary currents for both sides under balanced load. Set CT ratios to make them equal.
-
Other Protections:
-
Overcurrent: Back-up.
-
Restricted Earth Fault (REF): Sensitive protection for earth faults near neutral (only senses faults within transformer zone).
-
Buchholz Relay: For oil-filled transformers.
-
Temperature Monitoring: Winding temperature, oil temperature.
-
Busbar Protection
-
Importance: Busbar fault → massive outage, loss of multiple circuits.
-
Differential Protection Scheme:
-
CTs on all incoming/outgoing circuits.
-
Sum of CT currents should be zero under normal condition.
-
Internal fault → sum ≠ 0 → relay operates.
-
Challenge: CT saturation during external faults can cause false operation.
-
-
Frame Leakage Protection Scheme:
-
CTs on busbar frame/ground only.
-
Under normal, no current in frame CT.
-
Internal fault → fault current flows through frame → frame CT operates.
-
Simple, but not fail-safe (if frame insulation fails).
-
-
Other Methods:
-
High-Impedance Differential: Uses high series impedance to prevent maloperation during CT saturation.
-
Biased Differential: Similar to transformer differential, with slope to handle through faults.
-
Transmission Line Protection
-
Pilot Relaying Schemes: Use communication channel (pilot) between line ends for fast, selective tripping.
-
Types of Pilots:
-
Pilot Wires: Dedicated copper pairs. Reliable, fast, but expensive for long distances.
-
Power Line Carrier (PLCP): Uses transmission line itself as channel. Frequency: 30-500 kHz. Merits: No extra wires. Demerits: Attenuation, noise, requires coupling capacitors & line traps. Used for 33 kV to 220 kV.
-
Microwave: Point-to-point radio. Fast, reliable, independent of line. Used for EHV (400 kV+).
-
-
Phase Comparison Scheme (Carrier):
-
Compares phase of currents at both ends.
-
Operation: For internal fault, currents at both ends are in phase (both flow towards fault). Carrier signal sent → tripping. For external fault, currents out of phase → blocking.
-
Sketch: Shows CTs, phase comparator at each end, carrier transmitter/receiver, blocking/tripping logic.
-
-
-
Distance Protection:
-
Measures impedance $$\displaystyle Z = V/I $$ to fault.
-
MHO Relay is primary for Zone 1 (80-90% line length). OFF-SET MHO for Zones 2 & 3 (reach beyond line, with offset for high-resistance faults).
-
Protection Zones:
-
Zone 1: 80-90% of line. Instantaneous.
-
Zone 2: Covers remaining line + backup for next line (120-150% of line). Time delay (e.g., 0.5 s).
-
Zone 3: Backup for remote lines, and as last resort. Long reach, long delay (e.g., 1.0 s).
-
-
Current Limiting Reactors
-
Types: Air-core (dry, no saturation) and Iron-core (saturates at high current).
-
Construction: Series reactor installed in each feeder or at busbars.
-
Application: Limit fault current magnitude during short circuits. Protect equipment (breakers, cables) from high thermal/mechanical stress. Used in generator neutral, bus-section, and feeder applications.
-
Role: Increases system impedance, thereby reducing $$\displaystyle I_{fault} = E / (Z_{sys} + Z_{reactor}) $$.
V. AUXILIARY & OTHER PROTECTION DEVICES
High Rupturing Capacity (HRC Fuses)
-
Function: Fast, high-current interrupting device for LT switchgear.
-
Principle: Fusible element melts under overcurrent. Sand/quenching material surrounds element to cool arc and prevent restrike.
-
Application: Transformer protection (LT side), motor protection, capacitor banks.
Current Transformers (CTs) & Voltage Transformers (VTs)
-
CT Ratio Selection for Differential Protection:
-
Goal: Make CT secondary currents equal under normal load.
-
For Star-Delta Transformer:
-
HV side (Star): $$\displaystyle I_{HV, ph} = \frac{S}{\sqrt{3} V_{HV}} $$
-
LV side (Delta): $$\displaystyle I_{LV, line} = \frac{S}{\sqrt{3} V_{LV}} $$, $$\displaystyle I_{LV, ph} = I_{LV, line} / \sqrt{3} $$
-
Therefore, $$\displaystyle \frac{I_{HV, ph}}{I_{LV, ph}} = \frac{V_{LV}}{V_{HV}} \times \sqrt{3} $$
-
CT ratios must satisfy: $$\displaystyle \frac{\text{CT Ratio}_{HV}}{\text{CT Ratio}_{LV}} = \frac{V_{LV}}{V_{HV}} \times \sqrt{3} $$
-
-
-
CT Saturation: Occurs when primary current is so high that core flux exceeds saturation limit. Effect: CT secondary current is distorted (flattened) and inaccurate. Can cause failure of differential protection (through fault) or false operation (internal fault). Use Class X/TP CTs for protection.
Buchholz Relay (Detailed)
-
Location: Installed in the pipe between transformer tank and conservator.
-
Working Principle:
-
Gas Accumulation (Alarm): Minor internal faults generate gas. Gas collects in relay chamber → float drops → closes alarm contact.
-
Oil Surge (Trip): Major fault generates large volume of gas rapidly → oil surges towards conservator → deflects baffle plate → closes trip contact.
-
-
Protects: Against internal faults with oil decomposition (winding shorts, core faults). Does not protect against external faults or minor insulation deterioration without gas.
VI. SYSTEM & MODERN PROTECTION CONCEPTS
Security and Reliability
-
Reliability (Dependability): Relay must operate when required (for faults in its zone). False trips are unacceptable.
-
Security: Relay must not operate when not required (for faults outside zone or no fault). Failure to trip is unacceptable.
-
How Ensured:
-
Redundancy: Dual protection schemes (e.g., two independent differential relays).
-
Diversity: Different operating principles (e.g., differential + overcurrent).
-
Proper Setting & Coordination: Ensure selectivity.
-
Testing & Maintenance: Regular functional tests.
-
Logic in Numerical Relays: Blocking signals, timers, harmonic restraint (for transformer inrush).
-
Microprocessor-Based Protection Schemes
-
Advantages over Conventional:
-
Multiple functions in one unit (OC, distance, differential, autoreclose).
-
Adaptive settings (change with system conditions).
-
Self-monitoring & diagnostics.
-
Communication (SCADA, IEC 61850) for data, control, and event recording.
-
Advanced algorithms (Fourier, traveling wave).
-
Lower burden on CTs/VTs.
-
No drift (digital).
-
-
Implementation: Software executes protection logic. Hardware: ADC, DSP/CPU, memory, I/O, communication port.
Software Development for Protection
-
Role in Security & Reliability:
-
Secure Code: Prevents bugs causing false trips.
-
Verification & Validation (V&V): Extensive testing (simulation, hardware-in-loop).
-
Setting Management: Secure storage, easy retrieval, version control.
-
Fail-Safe Design: Watchdog timers, default safe states.
-
Cyber Security: Authentication, encryption for communication.
-
VII. CALCULATION & DESIGN PROBLEMS (INTEGRATED)
1. CT Ratio Calculation for Transformer Differential (Star-Delta)
Problem: 3-phase transformer 0.4 kV (Star) / 11 kV (Delta). CT ratio on LV side = 500/5. Find CT ratio on HV side.
-
Step 1: $$\displaystyle V_{LV} = 0.4 \ \text{kV} $$ (phase), $$\displaystyle V_{HV} = 11 \ \text{kV} $$ (line). For Star-Delta, $$\displaystyle V_{HV, ph} = 11 \ \text{kV} $$.
-
Step 2: Current ratio (line) $$\displaystyle I_{LV} / I_{HV} = 11 / 0.4 = 27.5 $$.
-
Step 3: CT secondary current should be equal. So, $$\displaystyle I_{HV, ph} \times \text{CT Ratio}_{HV} = I_{LV, line} \times \text{CT Ratio}_{LV} $$.
-
Step 4: But $$\displaystyle I_{HV, ph} = I_{HV, line} / \sqrt{3} $$. So:
$$ \frac{I_{HV, line}}{\sqrt{3}} \times \text{CT Ratio}_{HV} = I_{LV, line} \times 500/5 $$
$$ \Rightarrow \text{CT Ratio}_{HV} = \sqrt{3} \times \frac{I_{LV, line}}{I_{HV, line}} \times \frac{500}{5} = \sqrt{3} \times 27.5 \times 100 = 4762.5 $$
- Answer: $$\displaystyle \boxed{4762.5/5 \ \text{A} \ \text{or standard} \ 5000/5 \ \text{A}} $$
2. Fault Current Calculation for Unloaded Alternator
Problem: 25 MVA, 13.2 kV, solidly grounded. $$\displaystyle X_d'' = 0.25 $$ p.u., $$\displaystyle X_2 = 0.35 $$ p.u., $$\displaystyle X_0 = 0.1 $$ p.u. SLG fault at terminals. Find $$\displaystyle I_f $$ and line-to-line voltage.
-
Step 1: $$\displaystyle E_f = 1.0 $$ p.u. (reference). $$\displaystyle Z_1 = j0.25 $$, $$\displaystyle Z_2 = j0.35 $$, $$\displaystyle Z_0 = j0.1 $$.
-
Step 2: SLG fault: $$\displaystyle I_1 = I_2 = I_0 = \frac{1.0}{j(0.25+0.35+0.1)} = \frac{1}{j0.7} = -j1.4286 $$ p.u.
-
Step 3: Fault current: $$\displaystyle I_f = 3I_0 = 3 \times 1.4286 = 4.2857 $$ p.u.
-
Step 4: Convert to actual: Base current $$\displaystyle I_{base} = \frac{25 \times 10^6}{\sqrt{3} \times 13.2 \times 10^3} = 1092.4 \ \text{A} $$. $$\displaystyle I_f = 4.2857 \times 1092.4 = 4682 \ \text{A} $$.
-
Step 5: Line-to-line voltage (e.g., $$\displaystyle V_{bc} $$) during SLG fault (A-G):
$$ V_{bc} = V_{b0} + V_{b1} + V_{b2} $$
$$ V_1 = E_f - I_1 Z_1 = 1 - (-j1.4286 \times j0.25) = 1 - 0.3571 = 0.6429 \ \text{p.u.} $$
$$ V_2 = -I_2 Z_2 = -(-j1.4286 \times j0.35) = -0.5 \ \text{p.u.} $$
$$ V_0 = -I_0 Z_0 = -(-j1.4286 \times j0.1) = -0.1429 \ \text{p.u.} $$
For phase B: $$\displaystyle V_{b1} = a^2 V_1 $$, $$\displaystyle V_{b2} = a V_2 $$, $$\displaystyle V_{b0} = V_0 $$.
$$ V_{bc} = (V_{b1} - V_{c1}) + (V_{b2} - V_{c2}) + (V_{b0} - V_{c0}) $$
Since $$\displaystyle V_0 $$ is zero-sequence, $$\displaystyle V_{b0} - V_{c0} = 0 $$.
$$ V_{bc} = V_1(a^2 - a) + V_2(a - a^2) = (V_1 - V_2) j\sqrt{3} $$
$$ V_{bc} = (0.6429 - (-0.5)) j\sqrt{3} = 1.1429 \times j1.732 = j1.98 \ \text{p.u.} $$
Magnitude = **1.98 p.u.** (Line-to-line voltage rises during SLG fault!).
3. IDMT Relay Operation Time
Problem: 5 A, 2.2 s IDMT relay, plug setting 125%, TMS=0.6. CT 400/5. Fault current = 4000 A.
-
Step 1: Relay primary pick-up = $$\displaystyle 5 \ \text{A} \times 1.25 = 6.25 \ \text{A} $$.
-
Step 2: Fault current seen by relay = CT secondary current = $$\displaystyle 4000 \times (5/400) = 50 \ \text{A} $$.
-
Step 3: PSM = Fault current / Relay pick-up = $$\displaystyle 50 / 6.25 = 8 $$.
-
Step 4: For Standard Inverse (SI) curve: $$\displaystyle t = \frac{0.14 \times \text{TMS}}{(\text{PSM})^{0.02} - 1} = \frac{0.14 \times 0.6}{8^{0.02} - 1} $$.
$$\displaystyle 8^{0.02} = e^{0.02 \ln 8} = e^{0.02 \times 2.079} = e^{0.04158} = 1.0424 $$.
$$\displaystyle t = \frac{0.084}{0.0424} = 1.98 \ \text{s} $$.
-
Answer: $\boxed{t \approx 1.98 \ \text{seconds}}$
4. Percentage Differential Relay Stability Check
Problem: Stator protection, 15% slope. Fault: $$\displaystyle I_{CT1} = 400 \ \text{A} $$, $$\displaystyle I_{CT2} = 320 \ \text{A} $$. CT ratio = 500/5. Will relay trip?
-
Step 1: Bias/Through Current $$\displaystyle I_{through} = \frac{I_{CT1} + I_{CT2}}{2} = \frac{400+320}{2} = 360 \ \text{A} $$.
-
Step 2: Operating Current $$\displaystyle I_{op} = |I_{CT1} - I_{CT2}| = |400 - 320| = 80 \ \text{A} $$.
-
Step 3: Slope Setting: 15% means relay operates if $$\displaystyle I_{op} > 0.15 \times I_{through} $$.
$$\displaystyle 0.15 \times 360 = 54 \ \text{A} $$.
-
Step 4: Since $$\displaystyle I_{op} (80 \ \text{A}) > 54 \ \text{A} $$, relay will trip.
-
Note: CT ratio is same on both sides, so actual primary currents are proportional. Check is valid on secondary currents.
5. Per-Unit Reactance Conversion
Problem: Three generators on common bus. Convert to base: 200 MVA, 35 kV.
* G1: 100 MVA, 33 kV, 10%
* G2: 150 MVA, 32 kV, 8%
* G3: 110 MVA, 30 kV, 12%
-
Step 1: For each generator, calculate its own base current: $$\displaystyle I_{base,G} = S_{base,G} / (\sqrt{3} V_{base,G}) $$.
-
Step 2: Convert each reactance to new base using formula:
$$ X_{\text{new}} = X_{\text{old}} \times \frac{S_{base,\ \text{new}}}{S_{base,\ \text{old}}} \times \left( \frac{V_{base,\ \text{old}}}{V_{base,\ \text{new}}} \right)^2 $$
-
Calculations:
-
G1: $$\displaystyle X_1 = 0.10 \times \frac{200}{100} \times \left( \frac{33}{35} \right)^2 = 0.10 \times 2 \times 0.888 = 0.1776 $$ p.u.
-
G2: $$\displaystyle X_2 = 0.08 \times \frac{200}{150} \times \left( \frac{32}{35} \right)^2 = 0.08 \times 1.333 \times 0.836 = 0.0892 $$ p.u.
-
G3: $$\displaystyle X_3 = 0.12 \times \frac{200}{110} \times \left( \frac{30}{35} \right)^2 = 0.12 \times 1.818 \times 0.7347 = 0.160 $$ p.u.
-
-
Result: Reactance diagram: Three generators in parallel at common bus (35 kV), with $$\displaystyle X_1=0.1776 $$, $$\displaystyle X_2=0.0892 $$, $$\displaystyle X_3=0.160 $$ p.u. on 200 MVA, 35 kV base.
[!TIP]
Exam Focus: Be prepared to derive fault current expressions (especially DLG), calculate CT ratios for transformer differentials (Star-Delta is a favorite), compute IDMT times (memorize SI curve formula), and draw sequence networks for all fault types. For circuit breakers, compare SF6, VCB, and OCB. Always box final formulas and numerical answers.