Skip to content
EX-701 · Power System Protection/Quick Revision Short Notes

Power System Protection (EX-701) - Unit 3 Short Notes

UNIT 3: POWER SYSTEM PROTECTION


I. FUNDAMENTALS OF FAULT ANALYSIS & SYMMETRICAL COMPONENTS

1. Types of Power System Faults

  • Symmetrical (Balanced) Fault: Only Three-Phase Fault (LLL). All three phases short-circuited. System remains balanced. Least frequent but most severe.

  • Unsymmetrical (Unbalanced) Faults:

    • Single Line-to-Ground (LG): One phase to neutral/ground. Most common (~70%).

    • Line-to-Line (LL): Two phases short-circuited.

    • Double Line-to-Ground (DLG): Two phases to ground.

  • Causes: Insulation failure, lightning, wind, ice, human error, equipment failure.

  • Effects: Large fault currents, voltage dip, instability, equipment damage, fire hazard.

2. Concept of Symmetrical Components

  • Significance: Simplifies analysis of unbalanced 3-phase systems by resolving unbalanced phasors into three balanced sets:

    1. Positive Sequence: A₁, a²A₁, aA₁ (balanced, phase sequence A-B-C).

    2. Negative Sequence: A₂, a²A₂, aA₂ (balanced, phase sequence A-C-B).

    3. Zero Sequence: A₀, A₀, A₀ (all in phase, no phase displacement).

  • Operator 'a': $$\displaystyle a = 1 \angle 120^\circ = -\frac{1}{2} + j\frac{\sqrt{3}}{2} $$, $$\displaystyle a^2 = 1 \angle -120^\circ $$, $$\displaystyle a^3 = 1 $$, $$\displaystyle 1 + a + a^2 = 0 $$.

  • Transformation Matrix:

$$\begin{bmatrix} A_0 \\ A_1 \\ A_2 \end{bmatrix} = \frac{1}{3} \begin{bmatrix} 1 & 1 & 1 \\ 1 & a & a^2 \\ 1 & a^2 & a \end{bmatrix} \begin{bmatrix} A_a \\ A_b \\ A_c \end{bmatrix}$$

Inverse transformation is similar with matrix transpose (since matrix is symmetric).

3. Sequence Network Representation

  • Positive Sequence Network: Similar to steady-state equivalent, EMF = $$\displaystyle E_a $$ (pre-fault voltage), impedance = $$\displaystyle Z_1 $$ (sub-transient/transient reactance for generators).

  • Negative Sequence Network: No EMF source, impedance = $$\displaystyle Z_2 $$ (usually ≈ $$\displaystyle Z_1 $$ for syn. machines).

  • Zero Sequence Network: No EMF source, impedance = $$\displaystyle Z_0 $$. Path depends on grounding (e.g., solidly grounded gen: $$\displaystyle Z_0 $$ in series with neutral impedance $$\displaystyle Z_n $$).

  • Interconnection for Faults at Generator Terminals (Unloaded):

    | Fault Type | Sequence Network Connection | Fault Current Expression (Phase 'a') | |-----------------|-----------------------------------|-------------------------------------| | Three-Phase (LLL) | Only Positive Sequence | $$\displaystyle I_{f,a} = \frac{E_a}{Z_1} $$ | | Single LG | All 3 sequences in parallel | $$\displaystyle I_{f,a} = 3I_0 = \frac{3E_a}{Z_1+Z_2+Z_0} $$ | | Line-to-Line (LL) | Positive & Negative in parallel, Zero open | $$\displaystyle I_{f,a} = -I_{f,b} = \frac{\sqrt{3}E_a}{Z_1+Z_2} $$ | | Double LG (DLG) | Positive & Negative in parallel, this combo in series with Zero | $$\displaystyle I_{f,a} = \frac{3E_a}{Z_1 + \frac{Z_2Z_0}{Z_2+Z_0}} $$ |

4. Fault Current & Voltage Calculations

  • Key Formulas (Terminal Fault, Unloaded Gen):

    • LG Fault Current: $$\displaystyle I_{LG} = \frac{3E_a}{Z_1 + Z_2 + Z_0} $$

    • DLG Fault Current: $$\displaystyle I_{DLG} = \frac{\sqrt{3}E_a}{Z_1 + \frac{Z_2Z_0}{Z_2+Z_0}} $$

    • LLL Fault Current: $$\displaystyle I_{LLL} = \frac{E_a}{Z_1} $$

  • Fault Level / Fault MVA: $$\displaystyle S_{fault} = \sqrt{3} V_{pre-fault} I_{fault} $$. Represents short-circuit MVA at the fault point.

  • Effect of Fault Impedance (Z_f): Add $$\displaystyle Z_f $$ to the series combination of sequence networks in the fault path.

    • LG with Z_f: $$\displaystyle I_{f} = \frac{3E_a}{Z_1+Z_2+Z_0+3Z_f} $$
  • Line-to-Line Voltages during Fault: Can be found using sequence voltages: $$\displaystyle V_a = V_0 + V_1 + V_2 $$, etc.

5. Per Unit System & Reactance Diagram

  • Base Conversion: $$\displaystyle Z_{pu,new} = Z_{pu,old} \times \frac{(MVA_{new}/MVA_{old})}{(kV_{new}/kV_{old})^2} $$

  • Procedure for Multi-Machine System:

    1. Choose a common system base (MVA, kV).

    2. Convert each generator's reactance to this base.

    3. Draw all reactances on a single line diagram referred to a common voltage level (using transformer turns ratios).

Example (Nov 2023): Three generators on a common bus. Convert each to 200 MVA, 35 kV base, then draw pu reactance diagram.


II. PROTECTIVE RELAYS: PRINCIPLES & CHARACTERISTICS

1. Relay Operating Principles

Type Construction Operating Principle Applications Key Feature
Electromagnetic Attraction Plunger or attracted armature, coil (AC/DC) Magnetic force $$\displaystyle F \propto I^2 $$ pulls armature Simple overcurrent, under-voltage Fast, but prone to vibration on AC
Induction Disc Aluminum/copper disc in air-gap, two electromagnets (R & S) Torque $$\displaystyle T \propto I^2 \sin\phi $$ (φ = angle between R & S fluxes) Overcurrent, directional, distance Overrun: Disc inertia causes motion after current drops. Minimized by brake magnet.
Induction Cup Cylindrical cup (Al) in 4-pole field, 4 electromagnets Torque $$\displaystyle T \propto I_1 I_2 \sin\phi $$ (similar to disc) High-speed, differential, directional High reset-to-pickup ratio (~0.9), low overrun, sensitive.

2. Relay Characteristics & Settings

  • Time-Current Characteristics (IDMT):

$$t = \frac{TMS \times \beta}{(PSM^n - 1)}$$

Where:

*   $t$ = operating time (s)

*   $TMS$ = Time Multiplier Setting (0-1)

*   $PSM$ = Plug Setting Multiplier = $$\displaystyle \frac{\text{Fault Current}}{\text{Relay Rated Current} \times \text{Plug Setting}} $$

*   $\beta, n$ = constants depending on curve type:

    *   **Standard Inverse:** $$\displaystyle \beta=0.14 $$, $$\displaystyle n=0.02 $$

    *   **Very Inverse:** $$\displaystyle \beta=13.5 $$, $$\displaystyle n=1 $$

    *   **Extremely Inverse:** $$\displaystyle \beta=80 $$, $$\displaystyle n=2 $$

Exam Tip: Always compute PSM first. For DT relays, $$\displaystyle t = TMS \times \text{time dial setting} $$.

  • R-X Diagram Representation:

    • Impedance Relay: Circular characteristic. Operates when $$\displaystyle Z = \frac{V}{I} < Z_{set} $$. Offset circles for directional or to avoid 3rd zone issues.

    • MHO Relay (Admittance): Directional. Circle passing through origin. Operates when $$\displaystyle |Y| > |Y_{set}| $$ or $$\displaystyle Z < Z_{set} \cos(\theta - \theta_{char}) $$. More stable for long lines.

    • OFF-SET MHO: Two circles. Inner (reach) for Zone 1, outer (offset) for Zone 2/3. Prevents tripping for load impedance.

    • Directional Relay: Semicircle in R-X plane (e.g., for power relay, operates when $$\displaystyle \cos\phi > \cos\theta_{setting} $$).

3. Static Relays

  • Advantages: No moving parts, fast, accurate, multi-function, self-test, communication capable.

  • Functional Blocks:

    • Level Detector: Outputs 1 if input > setting. (e.g., Schmitt trigger).

    • Comparator: Compares two inputs.

      • Amplitude Comparator: $$\displaystyle |A| > |B| $$? (e.g., for overcurrent).

      • Phase Comparator: $$\displaystyle \angle(A-B) < \delta $$? (e.g., for directional).

    • Logic Circuits: AND, OR, NOT to combine outputs (e.g., trip = overcurrent AND directional).

    • Timer: Provides time delay (RC or digital).

  • Conversion: An amplitude comparator can be converted to phase comparator by passing one input through a 90° phase-shift network. Vice-versa using vector summation.

4. Microprocessor-Based / Numerical Relays

  • Block Schematic:

    
    CT/VT → Analog Input (filter, attenuator) → Sampler → A/D Converter → CPU (DSP) → Output (trip, alarm, comm)
    
    
  • Functions:

    • Protection: Implements all relay characteristics (IDMT, impedance, differential) via software.

    • Measurement: Records V, I, P, Q, frequency.

    • Monitoring: CT saturation, breaker status, health.

    • Communication: IEC 61850, SCADA integration.

  • Software Development: Focus on security (avoid nuisance trips), reliability (fail-safe), speed (real-time), self-check.

Exam Tip: Logic circuits in numerical relays replace hardware comparators. E.g., IF (I > Iset) AND (dir = forward) THEN trip.


III. CIRCUIT BREAKERS: THEORY, TYPES & SELECTION

1. Arc Phenomenon & Interruption Theory

  • Arc Formation: When contacts separate, ionization of medium creates low-resistance path.

  • Arc Quenching: Must cool & de-ionize arc column rapidly to prevent re-strike.

  • Recovery Voltage ($$\displaystyle v_r $$): System voltage across contacts after current zero. Transient Recovery Voltage (TRV): High-frequency oscillation superimposed on power-frequency recovery voltage. Critical for interruption.

  • Restriking Voltage: Voltage across contacts during arcing. High di/dt causes high restriking voltage.

  • Theory of Current Interruption: Energy Balance Concept – Arc extinguishes if rate of heat removal > rate of heat generation. At current zero, if dielectric strength of medium > recovery voltage, arc won't re-strike.

2. Types of Circuit Breakers

Type Principle Advantages Disadvantages Voltage Range
Oil (Bulk/Minimum) Arc in oil → gas bubble → quench Simple, cheap, oil acts as insulator & coolant Fire risk, maintenance, oil deterioration, slow Up to 400 kV (mostly obsolete)
Air Blast (Axial/Radial/Cross) High-pressure air blast across contacts Fast, no fire risk, good for autoreclose Current chopping, overvoltages, compressor needed 132-400 kV (historical)
SF₆ (Puffer/Self-Blast) SF₆ gas quenching (high electronegativity) Excellent – fast, compact, silent, low maintenance, high dielectric strength Gas handling, moisture sensitivity, cost 132 kV - 800 kV (dominant)
Vacuum Arc in vacuum → contact metal vapor → quench when contacts separate Very fast, long life, no gas, quiet, low maintenance Limited breaking capacity (~40 kA), cost for high kV Up to 38 kV (dominant in LT/HT distribution)

3. Ratings & Selection Criteria

  • Breaking Capacity: Max rms symmetrical current it can break at rated voltage. Asymmetrical breaking current = $$\displaystyle \sqrt{2} \times I_{sym} \times (1 + e^{-t/\tau}) $$ (where τ = L/R time constant).

  • Making Capacity: Max peak current it can close against (includes DC offset). Usually 1.8× symmetrical breaking current peak.

  • Selection Factors: Rated voltage/current, breaking/making capacity, duty cycle (O-0.3s-CO-3min-CO), application (transmission vs. distribution), TRV withstand, environmental conditions.

  • Testing: Type tests (thermal, dielectric, mechanical), routine tests.


IV. PROTECTION SCHEMES FOR POWER SYSTEM EQUIPMENT

1. Generator / Alternator Protection

  • Faults:

    • Stator: Phase-phase, phase-ground (LG). Protected by % Differential.

    • Rotor: Field winding ground, loss of excitation. Protected by field ground relay, loss-of-excitation relay (impedance).

    • Abnormal: Overcurrent, overvoltage, negative seq. (overheating), overheating (RTD), out-of-step.

  • Stator % Differential Protection:

    • Principle: Compare currents entering/leaving stator winding. $$\displaystyle I_{op} = |I_1 - I_2| $$, $$\displaystyle I_{rest} = |I_1 + I_2| $$. Trip if $$\displaystyle \frac{I_{op}}{I_{rest}} > \text{slope} $$.

    • Slope (bias): 15-30%. Prevents maloperation during through faults (CT mismatch, magnetizing current).

    • Numerical Check (Dec 2024): Slope = 15%. $$\displaystyle I_{CT1}=400A $$, $$\displaystyle I_{CT2}=320A $$. $$\displaystyle I_{op}=80A $$, $$\displaystyle I_{rest}=360A $$. Ratio = 22.2% > 15% → TRIP.

  • Generator-Transformer Unit Protection: Treat gen + transformer as one unit. One differential relay covers both. CTs on gen neutral and transformer HV side.

  • Buchholz Relay: Gas-actuated relay in transformer/generator oil conservator.

    • Incipient Faults: Minor overheating/arcing → gas bubbles → float operation → alarm.

    • Severe Faults: Oil surge → flap operation → trip.

2. Transformer Protection

  • Internal vs. External: Differential for internal; overcurrent/backup for external.

  • Merz-Price (Percentage Differential) for Star-Delta Transformer:

    • CT Ratio Selection: Must compensate for current magnitude (turns ratio) and phase shift (star-delta connection).

    • Formula: $$\displaystyle \frac{I_{HV}}{I_{LV}} = \frac{V_{LV}}{V_{HV}} \times \sqrt{3} $$ (due to delta-star).

    • CT Ratio Calculation (Dec 2025, Nov 2023):

      Given: Transformer 0.4/11 kV star-delta. LV CT ratio = 500/5. Find HV CT ratio.

$$I_{LV} = \frac{S}{\sqrt{3} \times 0.4}, \quad I_{HV} = \frac{S}{\sqrt{3} \times 11}$$

$$\frac{I_{HV}}{I_{LV}} = \frac{0.4}{11} = \frac{1}{27.5}$$

    LV CT secondary = 5A. For balance: HV CT secondary should also be 5A.

$$\text{HV CT ratio} = \frac{I_{HV}}{5} = \frac{I_{LV} / 27.5}{5} = \frac{500/5}{27.5} = \frac{100}{27.5} \approx 3.636$$

    So HV CT ratio ≈ **364/5 A** (or nearest standard).
  • Other Protections:

    • Restricted Earth Fault (REF): Sensitive earth fault protection for star-connected winding with grounded neutral.

    • Overfluxing: $V/f$ relay for geomagnetic storms or overvoltage.

    • Temperature: Oil temperature, winding temperature (RTDs).

3. Busbar Protection

  • Importance: Busbar fault → total station shutdown.

  • Differential Protection:

    • Principle: Sum of currents entering bus = 0 under normal. Fault → differential current.

    • Challenges: CT saturation during through faults → false differential. Use high-ratio CTs, high-impedance scheme.

  • Frame Leakage Protection:

    • Principle: Busbar enclosed in earthed metal frame. CT on frame earth connection. Fault → current flows through frame → earth CT operates.

    • Application: Simple, used for small substations.

  • High-Impedance Differential: Series-connected high resistor stabilizes against CT saturation.

  • Biased Differential: Similar to generator % diff, with slope to avoid through-fault maloperation.

4. Transmission Line Protection

  • Protection Zones (Distance Relay):

    • Zone 1: 80-90% of line length. No time delay (instantaneous).

    • Zone 2: Covers full line + 50% of next line. Time delay (0.3-0.5s) to coordinate with next line's Zone 1.

    • Zone 3: Backup for next two lines. Longer delay.

  • Distance Relays on R-X Diagram: Use impedance characteristics (MHO, offset MHO) to define zones as circles/quadrilaterals.

  • Pilot Protection Schemes:

    • Concept: Pilot = communication channel between line ends for fast, selective tripping.

    • Types:

      | Pilot Type | Medium | Range | Merits | Demerits | |------------|--------|-------|--------|----------| | Wire Pilot | Twisted pair | < 40 km | Simple, cheap | Susceptible to induced voltages, maintenance | | Carrier Current (PLCP) | Power line itself (40-500 kHz) | Up to 400 km | No extra wires, uses existing line | Filtering needed, limited to one channel, prone to interference | | Microwave | Radio link | Long | High speed, independent | Expensive, line-of-sight | | Fiber Optic | Optical fiber | Very long | High bandwidth, immune to EMI | Cost, fragility |

    • Power Line Carrier Protection (PLCP): Voltage range: 66 kV and above. Merits: Fast (≤ 30 ms), selective. Demerits: Requires tuning, blocking during switching, limited to one signal per line.

    • Phase Comparison Scheme (Carrier): Compare phase angles of currents at both ends. If both ends see fault in same direction → trip. Blocking type (trip if no blocking signal) more common.

  • Overcurrent Protection: For distribution lines (radial). Uses IDMT/DT relays with time-grading.


V. SPECIAL DEVICES & SYSTEM CONSIDERATIONS

1. Current-Limiting Reactors

  • Types:

    • Air-Core: No iron, linear inductance. Used in series with generators/feeders to limit fault current.

    • Iron-Core: With iron core, saturates at high current → less effective limiting.

  • Principle: Series reactance limits $$\displaystyle I_{fault} = \frac{E}{X} $$.

  • Location: Generator terminal, feeder inlet, busbar sections.

  • Application: Limit fault current to within breaker rating, protect equipment from mechanical/thermal stress.

2. Fuses

  • HRC (High Rupturing Capacity) Fuse:

    • Construction: Cercelain body, silver/copper element, quartz sand filling.

    • Working: Fault → element melts → arc in sand → sand quenches arc by cooling & high pressure.

    • Applications: LT switchgear, motor starters, transformers, capacitor banks. Replaceable element.

3. System Security & Reliability

  • Security: Avoid unwanted trips (maloperation). Ensured by:

    • Redundancy (dual systems).

    • Diversity (different technologies).

    • High-quality CTs/VTs, proper settings.

    • Blocking logic (e.g., in pilot schemes).

  • Reliability: Trip when required (correct operation). Ensured by:

    • Regular testing & maintenance.

    • Self-monitoring features in numerical relays.

    • Quality assurance in design/manufacture.

    • Adequate backup protection.

4. Protection of Specific Systems

  • Motor Protection:

    • Faults: Overload, short-circuit (phase-phase, phase-ground), single phasing.

    • Schemes: Thermal overload relay (bimetal), instantaneous overcurrent for short-circuit, negative sequence relay for unbalanced supply, under-voltage.

  • Feeder Protection: Overcurrent (radial), distance (transmission), pilot (important feeders).


KEY NUMERICAL PROBLEM AREAS - QUICK REFERENCE

  1. Fault Current Calculation:

    • Use sequence network interconnection.

    • $$\displaystyle I_{LG} = \frac{3E_a}{Z_1+Z_2+Z_0} $$ (with $$\displaystyle Z_f $$: add $$\displaystyle 3Z_f $$).

    • $$\displaystyle E_a $$ usually = 1 pu pre-fault voltage.

  2. CT Ratio for Transformer Differential (Star-Delta):

    • HV CT ratio = $$\displaystyle \frac{I_{HV}}{I_{sec}} $$; LV CT ratio = $$\displaystyle \frac{I_{LV}}{I_{sec}} $$.

    • $$\displaystyle \frac{I_{HV}}{I_{LV}} = \frac{V_{LV}}{V_{HV}} \times \sqrt{3} $$.

    • Set $$\displaystyle I_{sec} $$ same for both sides (usually 5A or 1A).

  3. IDMT Relay Operating Time:

    • $$\displaystyle PSM = \frac{I_f}{I_{pickup}} $$, where $$\displaystyle I_{pickup} = \text{Relay rating} \times \text{Plug Setting} $$.

    • $$\displaystyle t = \frac{TMS \times \beta}{(PSM^n - 1)} $$ (use correct $\beta,n$ for curve).

  4. % Differential Relay Stability Check:

    • $$\displaystyle I_{op} = |I_1 - I_2| $$, $$\displaystyle I_{rest} = |I_1 + I_2| $$.

    • Trip if $$\displaystyle \frac{I_{op}}{I_{rest}} \times 100\% > \text{slope}\% $$.

  5. Per Unit Conversion (Multi-Machine):

    • $$\displaystyle Z_{pu,new} = Z_{pu,old} \times \frac{MVA_{new}}{MVA_{old}} \times \left( \frac{kV_{old}}{kV_{new}} \right)^2 $$.

    • Convert all to common base before drawing diagram.

  6. Fault Level (MVA):

    • $$\displaystyle S_{fault} = \sqrt{3} \times V_{base} \times I_{fault} $$ (use base voltage and calculated fault current in pu or actual).

Final Exam Strategy: For derivation questions (e.g., DLG fault current), start with sequence networks, write KVL for each, solve for $$\displaystyle I_1 $$, then $$\displaystyle I_f $$. Always draw sequence network diagrams. For numerical problems, state assumptions (neglect resistance, unloaded system).

Go to where you left off?

Quick Add to Notes

Save questions, your own notes and screenshots into notes filed by unit. It takes a free account.

Create free account

Have an account? Log in