1.0 FUNDAMENTALS OF REFRIGERATION & CYCLE ANALYSIS
1.1 Tonne of Refrigeration (TR)
-
Definition: Cooling effect equivalent to melting 1 tonne (1000 kg) of ice at 0°C in 24 hours.
-
Units:
-
1 TR = 3.516 kW (SI)
-
1 TR = 12,000 Btu/h
-
-
Calculation:
$$ Q = m \times L_f = 1000 \, \text{kg} \times 335 \, \text{kJ/kg} = 335,000 \, \text{kJ/day} $$
$$ \text{TR} = \frac{335,000}{24 \times 3600} = 3.88 \, \text{kW} \approx 3.516 \, \text{kW (standard)} $$
-
[!TIP] Always use 3.516 kW/TR for conversions. Ice latent heat often taken as 335 kJ/kg or 144 Btu/lb.
1.2 Carnot Refrigeration Cycle & Heat Pump
-
COP Formulas (Temperatures in Kelvin):
-
Refrigeration: $$\displaystyle \boxed{\text{COP}_R = \frac{T_L}{T_H - T_L}} $$
-
Heat Pump: $$\displaystyle \boxed{\text{COP}_{HP} = \frac{T_H}{T_H - T_L}} $$
-
Heat Engine: $$\displaystyle \boxed{\eta = 1 - \frac{T_L}{T_H}} $$ (not COP)
-
-
Problem Solving:
-
Given $$\displaystyle T_L $$, $$\displaystyle T_H $$, and $$\displaystyle Q_{in} $$ (refrigeration) or $$\displaystyle Q_{out} $$ (heat pump):
-
Work input: $$\displaystyle W = \frac{Q_{in}}{\text{COP}_R} $$
-
For heat pump: $$\displaystyle Q_{out} = Q_{in} + W = Q_{in} \cdot \text{COP}_{HP} $$
-
-
-
[!TIP] COP<sub>HP</sub> = COP<sub>R</sub> + 1. Ensure temperatures are absolute (K).
1.3 Reversed Carnot Cycle - Ice Plant Problems
-
Process: Water cooled from initial temp → 0°C → frozen → subcooled ice.
-
Refrigeration Effect per kg:
$$ q_{evap} = C_{p,w}(T_{initial} - 0) + L_f + C_{p,ice}(0 - T_{storage}) $$
- Mass of Ice Produced:
$$ m_{ice} = \frac{Q_{total}}{q_{evap}} \quad \text{where } Q_{total} = \text{COP}_R \times W_{input} $$
- Power Requirement:
$$ W = \frac{m_{ice} \times q_{evap}}{\text{COP}_R} $$
-
[!TIP] If power given, find COP first from Carnot formula, then compute ice production.
1.4 Natural & Elementary Methods of Refrigeration
-
Ice Harvesting: Collecting natural ice from frozen lakes/rivers in winter, storing in insulated icehouses.
-
Evaporative Cooling: Water evaporation absorbs latent heat, cooling air. Effective in dry climates.
-
Nocturnal Radiation: Radiative cooling at night by exposing surfaces to sky (used in desert coolers).
-
Throttling (Joule-Thomson) Effect: Adiabatic expansion through a valve. Cooling occurs if gas is below inversion temperature (e.g., CO₂, NH₃ at room temp). Used in Linde process for liquefaction.
2.0 VAPOUR COMPRESSION REFRIGERATION SYSTEM (VCRS)
2.1 Theoretical Cycle Analysis on P-h, T-s, and P-V Diagrams
-
Processes:
-
1-2: Isentropic compression ($$\displaystyle s_1 = s_2 $$)
-
2-3: Constant pressure condensation (heat rejection)
-
3-4: Throttling ($$\displaystyle h_3 = h_4 $$, constant enthalpy)
-
4-1: Constant pressure evaporation (heat absorption)
-
-
Key Diagrams:
-
P-h: Throttling is vertical line; evaporation/condensation horizontal.
-
T-s: Isentropic compression vertical; throttling constant enthalpy diagonal.
-
P-V: Compression increases pressure, decreases volume.
-
-
[!TIP] On P-h chart, read enthalpies directly: $$\displaystyle h_1 $$ (evaporator exit), $$\displaystyle h_2 $$ (compressor exit), $$\displaystyle h_3 $$ (condenser exit), $$\displaystyle h_4 = h_3 $$ (after throttle).
2.2 Performance Parameters
- COP (ideal cycle):
$$ \text{COP} = \frac{\text{Refrigeration Effect}}{\text{Work Input}} = \frac{h_1 - h_4}{h_2 - h_1} $$
-
Effect of Suction Pressure (Evaporator temperature):
- Lower suction pressure → lower $$\displaystyle h_1 $$ (less refrigeration effect) and higher pressure ratio → higher $$\displaystyle h_2 $$ (more work) → COP decreases.
-
Effect of Discharge Pressure (Condenser temperature):
- Higher discharge pressure → higher $$\displaystyle h_2 $$ (more work) and possibly lower $$\displaystyle h_1 $$ if superheat changes → COP decreases.
-
[!TIP] For fixed condenser temp, lower evaporator temp always reduces COP. Optimize evaporator temp based on load.
2.3 Multistage Compression Systems
-
Purpose: Reduce discharge temperature, improve efficiency for high pressure ratios.
-
Liquid Intercooler:
-
Liquid from condenser is subcooled before entering second stage.
-
Reduces work input because vapor entering second stage has lower enthalpy.
-
-
Boot-strap Cycle:
-
Uses flash intercooling: liquid from condenser flashes in intercooler to cool vapor from first stage.
-
COP (approx):
-
$$ \text{COP} = \frac{h_1 - h_8}{(h_2 - h_1) + (h_4 - h_3)} $$
(States: 1=evap exit, 2=1st stage comp exit, 3=after intercooler liquid, 4=flash vapor, 8=throttle exit)
-
DiagramCANVAS: Boot-strap cycle with two compressors, intercooler with flash chamber, condenser, evaporator, throttle valves. Show pressure levels: P1 (evap), P2 (intermediate), P3 (condenser).
-
[!TIP] Boot-strap avoids external intercooling; uses internal flash cooling.
2.4 Comparison: Multi-stage Compression vs. Cascade System
| Aspect | Multi-stage Compression | Cascade System |
|---|---|---|
| Refrigerant | Same refrigerant in all stages | Different refrigerants in each cycle |
| Intercooling | Liquid or flash intercooling | Intermediate heat exchanger |
| Pressure Ratio | Divided among stages | Each cycle has moderate pressure ratio |
| Temperature | Can achieve low temps but limited | Very low temps (< -40°C) possible |
| Complexity | Simpler (one system) | More complex (two independent systems) |
| Application | Moderate pressure ratios | Ultra-low temperature applications |
2.5 Practical Vapour Compression Cycle
-
Superheating:
-
Vapor at evaporator exit > saturation temperature.
-
Increases refrigeration effect ($$\displaystyle h_1 $$ increases) but also work ($$\displaystyle h_2 $$ increases).
-
Net COP may increase or decrease; generally beneficial if superheat is moderate.
-
-
Subcooling (Undercooling):
-
Liquid at condenser exit < saturation temperature.
-
Increases refrigeration effect ($$\displaystyle h_4 $$ decreases) without extra work → COP increases.
-
-
Combined Effect: Superheat + subcooling usually improves COP significantly.
3.0 VAPOUR ABSORPTION REFRIGERATION SYSTEM (VARS)
3.1 Basic Principle & Comparison with VCRS
-
VCRS: Mechanical compressor raises pressure of refrigerant vapor.
-
VARS:
-
Absorber dissolves refrigerant vapor in absorbent (low pressure).
-
Pump increases pressure of solution (liquid, so little work).
-
Generator heats solution to separate refrigerant vapor.
-
-
Function Achieved: Compressor replaced by absorber (low side) and pump + generator (high side).
3.2 Practical Vapour Absorption Cycle
-
Components:
-
Generator: Heat input → strong solution → weak solution + vapor.
-
Condenser: Vapor condenses to liquid.
-
Evaporator: Liquid evaporates, providing refrigeration.
-
Absorber: Vapor absorbed by weak solution → strong solution.
-
Pump: Pressurizes strong solution to generator pressure.
-
Throttle valve: Drops pressure from generator to absorber.
-
Solution heat exchanger: Recovers heat from hot strong solution to preheat weak solution → improves COP.
-
-
[!TIP] COP of VARS is lower than VCRS (0.5-0.7 vs 3-6) but economical with waste heat/solar.
3.3 Aqua-Ammonia (NH₃-H₂O) System
-
Refrigerant: Ammonia (NH₃)
-
Absorbent: Water (H₂O)
-
Working:
-
Strong NH₃-H₂O solution pumped to generator.
-
Heated (by steam/solar) → NH₃ vapor separates, weak solution returns to absorber.
-
NH₃ vapor condenses, throttles, evaporates in evaporator.
-
NH₃ vapor absorbed in absorber by weak solution, releasing heat.
-
-
DiagramCANVAS: Aqua-ammonia absorption system: generator (top), condenser (right), evaporator (bottom), absorber (left). Solution pump between absorber and generator, throttle between generator and absorber, solution heat exchanger in solution line. Arrows show flow: strong solution up to generator, weak solution down to absorber, refrigerant vapor from generator to condenser to evaporator to absorber.
-
Properties of Ideal Pair: High solubility, low heat of mixing, chemical stability, no crystallization.
3.4 Lithium Bromide (LiBr-H₂O) System
-
Refrigerant: Water (H₂O)
-
Absorbent: Lithium Bromide (LiBr)
-
Working: Similar to aqua-ammonia but water evaporates at low pressure. LiBr solution absorbs water vapor.
-
Applications: Large capacity air conditioning (100+ TR) in hotels, hospitals, where waste heat or solar available.
-
Challenges: LiBr crystallizes at high concentration, requires vacuum operation, corrosive → need inhibitors.
-
DiagramCANVAS: LiBr-H₂O absorption system: similar layout but refrigerant is water. Evaporator provides chilled water for AC. Generator heated by steam/ hot water. Absorber cooled by cooling water.
3.5 Advantages of VARS over VCRS
-
Utilizes low-grade heat (waste heat, solar energy, gas flame).
-
Quiet operation (no compressor noise).
-
Fewer moving parts (only pump and valves) → less maintenance.
-
Suitable for remote areas with heat source but no reliable electricity.
-
[!TIP] VARS ideal where electricity is expensive/unavailable but heat is free (e.g., industrial waste heat, solar thermal).
4.0 REFRIGERANTS
4.1 Classification of Refrigerants
-
Primary vs Secondary:
-
Primary: Directly circulate in refrigeration system (e.g., R-12, NH₃).
-
Secondary: Carry heat to primary (e.g., brine, water, glycol solutions).
-
-
Chemical Classification:
-
Halocarbons:
-
CFCs (R-11, R-12) – ODP high, banned.
-
HCFCs (R-22) – ODP low, transitional.
-
HFCs (R-134a, R-404A) – ODP zero, GWP high.
-
-
Azeotropes: Mixtures behaving as single substance (e.g., R-500 = R-12/R-152a).
-
Inorganic: NH₃ (R-717), CO₂ (R-744), H₂O (R-718).
-
Hydrocarbons: Propane (R-290), Isobutane (R-600a) – flammable, low GWP.
-
4.2 Desirable Properties of an Ideal Refrigerant
-
Thermodynamic:
-
Low boiling point (for low evaporator temp).
-
High latent heat (large refrigeration effect per kg).
-
High critical temperature/pressure (allows higher condensing temp, better COP).
-
Low specific volume (reduces compressor size).
-
-
Chemical:
-
Non-toxic, non-flammable, non-corrosive.
-
Chemically stable (no decomposition at high temps).
-
Miscible with lubricating oil.
-
-
Physical:
-
Low viscosity, high thermal conductivity.
-
Low specific heat (for better throttling cooling effect).
-
4.3 Factors for Refrigerant Selection
-
Application:
-
Cold storage: NH₃, R-404A.
-
Air conditioning: R-22, R-134a, R-410A.
-
Cascade systems: Low GWP refrigerants (CO₂, NH₃).
-
Domestic refrigerators: HCs (R-600a), HFCs (R-134a).
-
-
Safety: Toxicity, flammability, ASHRAE safety classifications (A1, A2L, B2, etc.).
-
Environmental Impact: ODP, GWP.
-
Compatibility: With materials (elastomers, metals) and lubricants.
-
Cost and Availability.
4.4 Specific Refrigerants
-
Ammonia (NH₃, R-717):
-
Properties: High latent heat (1370 kJ/kg at -10°C), good thermophysical, toxic (TLV 25 ppm), flammable (flammable at 15-28% in air), strong odor (detectable).
-
Applications: Industrial refrigeration, cold storage, ice plants.
-
Advantages: High COP, leaks easily detectable, inexpensive.
-
Disadvantages: Toxic, corrosive to copper/brass, requires steel components, not for domestic AC.
-
-
R-12 (CCl₂F₂):
-
ODP = 1.0 (reference), GWP = 10,900. Banned by Montreal Protocol.
-
Used in old domestic refrigerators, car AC.
-
-
R-22 (CHClF₂):
-
ODP = 0.05, GWP ≈ 1810. Being phased out (HCFC).
-
Used in AC, chillers, heat pumps.
-
-
Refrigerant Numbering:
-
R-22: CHClF₂ → 1 carbon, 1 H, 1 Cl, 1 F → 22.
-
R-134a: CH₂FCF₃ → C₂H₂F₄ → 134a (1=C-1, 3=H+1, 4=F, 'a' isomer).
-
R-717: 7 = inorganic, 17 = molecular weight of NH₃ (17).
-
4.5 Environment-Friendly Refrigerants (Eco-friendly)
-
HFCs (e.g., R-134a, R-404A, R-410A):
-
ODP = 0, but high GWP (R-134a GWP=1430).
-
Used as CFC/HCFC replacements but being phased down under Kigali Amendment.
-
-
Hydrocarbons (HCs) (e.g., R-290 propane, R-600a isobutane):
-
ODP = 0, GWP very low (R-290 GWP=3), flammable.
-
Used in small appliances (refrigerators, ACs < 5 TR).
-
-
Natural Refrigerants:
-
CO₂ (R-744): ODP=0, GWP=1, high pressure (up to 100 bar), used in cascade and transcritical systems.
-
NH₃ (R-717): ODP=0, GWP=0, toxic but excellent thermophysical.
-
H₂O (R-718): ODP=0, GWP=0, used in steam jet and absorption.
-
-
Regulations:
-
Montreal Protocol (1987): Phase-out of CFCs, HCFCs.
-
Kyoto Protocol (1997): Targets for GHG reduction, affecting high-GWP HFCs.
-
Kigali Amendment (2016): Phase-down of HFCs globally.
-
-
[!TIP] For new systems, prefer low-GWP options: HCs for small capacity, CO₂ for commercial, NH₃ for industrial. Check safety class (A2L, A3).
5.0 PSYCHROMETRICS & AIR CONDITIONING PROCESSES
5.1 Psychrometric Terms & Definitions
-
Dry Bulb Temperature (DBT): Measured by ordinary thermometer.
-
Wet Bulb Temperature (WBT): Temperature read by thermometer with wet wick, indicates moisture content.
-
Dew Point Temperature (DPT): Temperature at which air becomes saturated (RH=100%) when cooled at constant pressure.
-
Relative Humidity (RH): $$\displaystyle \phi = \frac{p_v}{p_{sat}(T_{DB})} \times 100\% $$, where $$\displaystyle p_v $$ = partial pressure of vapor.
-
Specific Humidity (Humidity Ratio, ω): Mass of water vapor per kg dry air:
$$ \omega = 0.622 \frac{p_v}{p - p_v} \quad \text{(kg water/kg dry air)} $$
-
Saturated Air: RH = 100%, DBT = DPT = WBT.
-
Enthalpy of Moist Air (approx):
$$ h = 1.006 T_{DB} + \omega (2501 + 1.86 T_{DB}) \quad \text{(kJ/kg dry air)} $$
5.2 Psychrometric Processes on Chart
-
Sensible Heating/Cooling: Constant ω (vertical line on chart with DBT vertical, ω horizontal). Heat added/removed without moisture change.
-
Humidification: Adding moisture. At constant DBT → horizontal line to right; at constant WBT → along constant wet-bulb line.
-
Dehumidification: Removing moisture. Cooling below dew point → condensation.
-
Cooling and Dehumidification Process:
-
Air cooled below dew point, moisture condenses.
-
Process line is straight with negative slope, parallel to constant wet-bulb lines.
-
Ends at saturation if coil temperature below dew point.
-
DiagramCANVAS: Psychrometric chart showing cooling and dehumidification from state A to state B. Line slopes downward left, crossing saturation curve at Apparatus Dew Point (ADP).
-
-
Heating and Dehumidification: Heating while removing moisture (e.g., heating coil with dehumidification) – process moves right and up.
5.3 Air Mixing Problems
-
Two-stream mixing (recirculated + fresh air):
-
Mass balance dry air: $$\displaystyle m_{da,1} + m_{da,2} = m_{da,m} $$
-
Humidity ratio: $$\displaystyle \omega_m = \frac{m_1 \omega_1 + m_2 \omega_2}{m_1 + m_2} $$
-
Enthalpy: $$\displaystyle h_m = \frac{m_1 h_1 + m_2 h_2}{m_1 + m_2} $$
-
Find $$\displaystyle T_m $$, $$\displaystyle \phi_m $$ from chart using $$\displaystyle \omega_m $$ and $$\displaystyle h_m $$.
-
-
[!TIP] For volume flow rates (m³/min), convert to mass flow using density at given conditions or use volume-based mixing if pressures equal.
5.4 Cooling Coil Performance
-
Apparatus Dew Point (ADP):
-
Temperature at which air would be saturated if cooled along constant wet-bulb line to saturation.
-
Represents effective coil surface temperature if coil is 100% effective.
-
-
Bypass Factor (BPF):
-
Fraction of air that bypasses coil without contacting it.
-
$$ \text{BPF} = \frac{h_1 - h_3}{h_1 - h_2} = \frac{\omega_1 - \omega_3}{\omega_1 - \omega_2} = \frac{T_1 - T_3}{T_1 - T_2} \text{ (approx)} $$
-
Where: 1 = inlet, 2 = ADP state (saturated at ADP), 3 = outlet.
-
Outlet State given BPF and ADP:
-
$$\displaystyle h_3 = h_1 - \text{BPF} (h_1 - h_2) $$
-
$$\displaystyle \omega_3 = \omega_1 - \text{BPF} (\omega_1 - \omega_2) $$
-
Find $$\displaystyle T_3 $$, $$\displaystyle \phi_3 $$ from chart.
-
-
[!TIP] BPF = 0 → all air contacts coil, outlet = ADP state. BPF = 1 → no contact, outlet = inlet.
5.5 Summer Air Conditioning Load Calculation
- Sensible Heat Factor (SHF):
$$ \text{SHF} = \frac{Q_{sens}}{Q_{total}} = \frac{C_{p,da} (T_{mixed} - T_{supply})}{h_{mixed} - h_{supply}} $$
-
Grand Sensible Heat Factor (GSHF): SHF of mixed air before coil (considering outdoor + recirculated).
-
Total Cooling Load:
$$ Q_{total} = \dot{m}_{da} (h_{mixed} - h_{supply}) \quad \text{(kW)} $$
- Sensible Load:
$$ Q_{sens} = \dot{m}_{da} C_{p,da} (T_{mixed} - T_{supply}) \quad \text{(kW)} $$
- Latent Load:
$$ Q_{lat} = Q_{total} - Q_{sens} $$
- Mass of Water Condensed:
$$ \dot{m}_{cond} = \dot{m}_{da} (\omega_{mixed} - \omega_{supply}) \quad \text{(kg/h or kg/s)} $$
- Cooling Coil Capacity in TR:
$$ \text{Capacity (TR)} = \frac{Q_{total} \text{ (kW)}}{3.516} $$
-
[!TIP] Always compute $$\displaystyle \omega_{mixed} $$ and $$\displaystyle h_{mixed} $$ from mixing calculation, then apply SHF/GSHF to find supply conditions or loads.
5.6 Comfort vs. Industrial Air Conditioning
| Aspect | Comfort Air Conditioning | Industrial Air Conditioning |
|---|---|---|
| Temperature | 20–24°C (summer), 20–22°C (winter) | As per process requirement (e.g., 10°C for printing) |
| Relative Humidity | 40–60% | Varies widely (e.g., < 50% for textiles, > 60% for food) |
| Air Purity | High (dust, odor free) | May tolerate lower purity (e.g., workshops) |
| Air Movement | 0.15–0.2 m/s (draft-free) | May require higher velocities for dilution |
| Objective | Human comfort | Process/product quality, equipment protection |
| Factors Affecting | Activity level, clothing, air velocity, humidity | Specific process needs, contamination control |
6.0 SPECIAL REFRIGERATION SYSTEMS & APPLICATIONS
6.1 Steam Jet Refrigeration System
-
Working Principle:
-
High-pressure steam expands through nozzle, creates vacuum in mixing chamber.
-
Low-pressure vapor from evaporator is entrained and compressed by steam jet.
-
Mixed vapor condenses in condenser; condensate returned to boiler.
-
DiagramCANVAS: Steam jet refrigeration: steam nozzle, mixing chamber, evaporator, condenser. Arrows: steam → nozzle → mixing → condenser; refrigerant vapor from evaporator → mixing → condenser.
-
-
T-s and H-s Diagrams:
-
T-s: Steam expansion isenthalpic? Actually steam expands isentropically in nozzle, then mixes. Refrigerant vapor compressed.
-
H-s: Shows steam expansion and refrigerant compression.
-
-
Advantages: No moving parts, simple, uses waste steam.
-
Limitations: Very low COP (0.1–0.3), high steam consumption, requires high-pressure steam source.
-
[!TIP] Used where waste steam is available, e.g., sugar mills, chemical plants.
6.2 Cascade Refrigeration System
-
Working:
-
Two independent cycles with different refrigerants.
-
Low-Temperature (LT) Cycle: Evaporator cools space, condenser rejects heat to cascade heat exchanger.
-
High-Temperature (HT) Cycle: Evaporator absorbs heat from cascade heat exchanger, condenser rejects to ambient.
-
Cascade Heat Exchanger: Allows heat transfer between LT condenser and HT evaporator.
-
-
DiagramCANVAS: Cascade system: LT cycle (evaporator → LT comp → LT condenser → cascade HX → throttle → LT evap). HT cycle (cascade HX → HT comp → HT condenser → throttle → HT evap). Cascade HX between LT condenser and HT evaporator.
-
Comparison with Multistage:
-
Cascade: Different refrigerants, separate compressors, intermediate heat exchanger. For very low temps (< -40°C).
-
Multistage: Same refrigerant, intercooling between stages. For moderate pressure ratios.
-
-
[!TIP] Cascade avoids high compression ratios in one stage; allows optimal refrigerants for each temperature level.
6.3 Aircraft Refrigeration (Air Cycle System)
-
Problem: High altitude air is cold (e.g., 263 K at 8000 m) but at low pressure; cabin needs pressurization and cooling.
-
Bootstrap Cycle:
-
Bleed air from engine compressor → aftercooler → compressor (increases pressure) → aftercooler → expansion turbine (cools) → air to cabin.
-
Some air bled off for cooling before turbine (reduced ambient).
-
DiagramCANVAS: Bootstrap cycle: ambient air → compressor → aftercooler → turbine → cabin. Cooling turbine provides refrigeration. Bleed air from compressor may be used for cabin pressurization.
-
-
Reduced Ambient Cooling: Use ram air (high-altitude cold air) directly for cooling without compression.
-
Calculations (per kg air):
-
Power for Pressurization: Compressor work $$\displaystyle W_c = C_p (T_{2s} - T_1)/\eta_c $$ (isentropic efficiency).
-
Refrigeration Effect: $$\displaystyle q_{evap} = C_p (T_3 - T_4) $$ after expansion (isentropic efficiency considered).
-
Given: altitude pressure $$\displaystyle p_a $$, temperature $$\displaystyle T_a $$, aircraft speed $V$ (ram effect), compression ratio $$\displaystyle r_p $$, cabin pressure $$\displaystyle p_c $$, cabin temperature $$\displaystyle T_c $$.
-
-
[!TIP] In aircraft, air is the refrigerant (dense air system). Use isentropic relations for compression and expansion with efficiencies.
6.4 Applications of Refrigeration for Food Preservation
-
Controls:
-
Microbial Growth: Low temperature slows bacterial/mold growth.
-
Enzyme Activity: Reduces enzymatic browning, ripening.
-
Respiration: Slows metabolic rate in fresh produce.
-
-
Methods:
-
Cold Storage: 0–4°C for vegetables, fruits.
-
Chilling: 0–4°C for meat, fish.
-
Freezing: -18°C to -30°C for long-term storage.
-
Ice Production: For direct cooling, preservation during transport.
-
-
[!TIP] Freezing point depression for fish/meat; blast freezing for quality.
7.0 AUXILIARY TOPICS & MISCELLANEOUS
7.1 Fog in Air Conditioning
-
Definition: Visible mist formed when air becomes supersaturated (RH > 100%) and water vapor condenses into tiny droplets.
-
Cause:
-
Over-cooling air below its dew point in cooling coil.
-
Mixing of cold, dry air with warm, humid air.
-
-
Psychrometric Representation:
-
When two air streams mix, if the mixed state lies on the saturation curve, fog forms.
-
Cooling coil process: If ADP is very low and BPF high, outlet may be on saturation curve → fog at coil exit.
-
-
[!TIP] Fog occurs when air is saturated and contains excess moisture; avoid by ensuring outlet air RH < 100% (control ADP or BPF).
7.2 Leak Detection Methods for Refrigerants
-
Soap Solution: Apply to joints; bubbles indicate leak. Simple, cheap.
-
Electronic Leak Detector: Sniffs refrigerant, gives audible/visual signal. Sensitive to halocarbons.
-
UV Dye: Add fluorescent dye to system; inspect with UV light after circulation.
-
Halide Torch: For halocarbons (CFCs/HCFCs); flame turns green if refrigerant present.
-
[!TIP] For HFCs (no chlorine), use electronic detector or UV dye. Soap solution works for any gas.
7.3 Production of Dry Ice (Solid CO₂)
-
Process:
-
Liquefaction: CO₂ gas compressed and cooled to liquid at high pressure (~60 bar).
-
Flashing: Liquid CO₂ released to atmospheric pressure → flashes to solid (snow) and gas (sublimation).
-
Pelletizing/Blocking: Solid compressed into pellets or blocks.
-
-
Applications: Food transport, medical cooling, fog effects.
-
[!TIP] Dry ice sublimes at -78.5°C; handle with gloves to avoid frostbite.
7.4 Electrolux (Water-Lithium Bromide Absorption) System - Brief Note
-
Type: LiBr-H₂O absorption refrigeration.
-
Working: Similar to aqua-ammonia but refrigerant is water, absorbent is LiBr.
-
Features:
-
Generator heated by steam/solar.
-
Evaporator produces chilled water for AC.
-
Absorber cooled by cooling water.
-
Used in large-capacity air conditioning (e.g., hotels, hospitals).
-
-
Advantages: Quiet, uses waste heat.
-
Disadvantages: LiBr crystallizes, requires vacuum, corrosive.
-
DiagramCANVAS: Electrolux system: generator (heated), condenser, evaporator (chilled water), absorber (cooling water), solution pump, throttle, solution heat exchanger.
7.5 Dense Air vs. Open Air Refrigeration System (Aircraft)
-
Open Air System: Ambient air at altitude (low pressure) used directly for cooling after expansion. Requires large volumes, inefficient.
-
Dense Air System: Air compressed first (increasing pressure and density), then cooled and expanded. More compact, efficient.
-
Aircraft Application: Bootstrap cycle is a dense air system.
-
Advantages: Higher density → smaller components, better control of cabin pressure and temperature.
-
Disadvantage: Requires compressor work (bleed air from engine).
-
-
[!TIP] All modern aircraft use dense air (boot-strap or reduced ambient) for both pressurization and cooling.