Skip to content
EX-601 · Power System‑II/Quick Revision Short Notes

Power System‑II (EX-601) - Unit 4 Short Notes

UNIT 4: POWER SYSTEM ANALYSIS, STABILITY, CONTROL & ECONOMIC OPERATION


1.0 POWER SYSTEM STRUCTURE & INTERCONNECTION

1.1 Necessity and Benefits of Interconnected Power Systems

  • Necessity: To ensure reliable, continuous, and economical power supply by sharing generation reserves, load diversity, and accessing remote energy resources.

  • Key Benefits:

    • Reliability: Mutual aid during contingencies (N-1 criterion).

    • Economy: Utilization of most efficient plants (economic dispatch over a larger area), reduced spinning reserve.

    • Improved Voltage & Frequency: Larger system inertia helps damp frequency fluctuations; reactive power support is easier.

    • Access to Remote Resources: Hydro, wind, solar farms far from load centers can be connected.

1.2 Problems Associated with Interconnected Systems

  • Complexity: Protection coordination, stability analysis, and control become significantly more difficult.

  • Stability Issues: Interarea oscillations, risk of cascading failures.

  • Regulatory & Commercial: Need for open access, wheeling charges, and settlement mechanisms in a deregulated environment.

  • Synchronism Loss: A major disturbance in one area can cause instability and loss of synchronism across the interconnection.

1.3 Modern Power System Concepts

  • 1.3.1 Deregulation & Restructuring: Separation of generation, transmission, and distribution (unbundling). Introduction of competition in generation and retail supply. Open Access allows any generator/consumer to use the transmission network for a fee.

  • 1.3.2 Distributed Generation (DG): Small-scale generation (solar PV, wind, microturbines) located close to the load center. Impacts power flow, voltage profile, and protection schemes.

  • 1.3.3 Transmission Open Access (TOA): Non-discriminatory use of the transmission network by all market participants, governed by a central system operator.

[!TIP] Exam Focus: Be prepared to explain why interconnection is needed (benefits) and what new problems it introduces (stability, coordination, deregulation challenges).


2.0 LOAD FLOW ANALYSIS (POWER FLOW STUDIES)

2.1 Significance and Objectives

  • Determines voltage magnitudes and angles at all buses, and real & reactive power flows in all lines for a given generation and load condition.

  • Objectives: Planning (new lines, capacity), Operation (optimal dispatch, contingency analysis), Stability studies (initial operating point).

2.2 Classification of Buses

Bus Type Known Quantities Unknown Quantities Purpose
Slack/Swing Bus V , δ
PV Bus V , P
PQ Bus P, Q V
  • Justification: Only one slack bus is needed as the reference. Generator buses with AVR are PV buses. All other buses are PQ buses.

2.3 Formation of Admittance Matrix (Y<sub>BUS</sub>)

  • Element-by-Element Addition Method:

    1. Start with a zero matrix.

    2. For each line k between buses i and j with series impedance z_series = R + jX:

      • Y_ii += 1/z_series

      • Y_jj += 1/z_series

      • Y_ij = Y_ji = -1/z_series

    3. For a shunt element (line charging jB/2 at each end):

      • Y_ii += jB/2

      • Y_jj += jB/2

    • Result: Symmetric, sparse matrix.
  • Direct Formation: From network data using the above rules systematically.

Example Problem (Y<sub>BUS</sub> Formation): Given 4-bus system with line impedances (p.u.), neglect shunt capacitance.

DiagramCANVAS: Draw a simple 4-bus diagram with lines 1-2, 1-3, 1-4, 2-3, 3-4. Label impedances as per data.

Solution Steps:

  1. Y_12 = 1/(0.25+j0.1) = 3.882 - j1.553 p.u.
  1. Y_13 = 1/(0.20+j0.8) = 1.176 - j4.706 p.u.
  1. Y_14 = 1/(0.30+j1.2) = 0.784 - j3.137 p.u.
  1. Y_23 = 1/(0.20+j0.8) = 1.176 - j4.706 p.u.
  1. Y_34 = 1/(0.15+j0.6) = 1.569 - j6.275 p.u.
  1. Assemble Ybus:
*   `Y_11 = Y_12 + Y_13 + Y_14`
*   `Y_22 = Y_12 + Y_23`
*   `Y_33 = Y_13 + Y_23 + Y_34`
*   `Y_44 = Y_14 + Y_34`
*   Off-diagonals are negatives of mutual admittances.

2.4 Load Flow Solution Methods

Feature Gauss-Seidel (GS) Newton-Raphson (NR) Fast Decoupled (FDLF)
Convergence Slow, linear Fast, quadratic Very fast
Memory Less More Less
Complexity Simple Complex (Jacobian) Simplified Jacobian
Suitability Small systems All systems Well-behaved, high-voltage systems
Coordinate Usually Polar Rectangular or Polar Polar

Gauss-Seidel Method (PQ Buses only):

For each PQ bus i, update voltage:

$$ V_i^{(k+1)} = \frac{1}{Y_{ii}} \left( \frac{P_i - jQ_i}{V_i^{(k)*}} - \sum_{j=1, j\neq i}^{n} Y_{ij} V_j^{(k)} \right) $$

  • Iterate until $$\displaystyle |V_i^{(k+1)} - V_i^{(k)}| < \epsilon $$ for all buses.

  • PV Bus Handling: Calculate Q from latest voltage. If Q exceeds limits, convert to PQ bus for that iteration.

Newton-Raphson Method:

  • Rectangular Coordinates: Solve for ΔP, ΔQ in terms of Δe, Δf.

$$ \begin{bmatrix} \Delta P \\ \Delta Q \end{bmatrix} = \begin{bmatrix} J_{11} & J_{12} \\ J_{21} & J_{22} \end{bmatrix} \begin{bmatrix} \Delta e \\ \Delta f \end{bmatrix} $$

where Jacobian sub-blocks involve partial derivatives.
  • Polar Coordinates: Solve for ΔP, ΔQ in terms of Δ|V|, Δδ. More common.

$$ \begin{bmatrix} \Delta P \\ \Delta Q \end{bmatrix} = \begin{bmatrix} \frac{\partial P}{\partial \delta} & \frac{\partial P}{\partial |V|} \\ \frac{\partial Q}{\partial \delta} & \frac{\partial Q}{\partial |V|} \end{bmatrix} \begin{bmatrix} \Delta \delta \\ \Delta |V| \end{bmatrix} $$

  • Flow: Form Ybus → Calculate P, Q, mismatches → Form Jacobian → Solve for corrections → Update voltages → Repeat.

[!TIP] Common Pitfall: In GS, convergence is slow for large systems. In NR, initial guess must be close; singularity in Jacobian if slack bus is not properly defined.


3.0 POWER SYSTEM STABILITY

3.1 Fundamental Concepts

  • Stability: Ability of a power system to regain a state of operating equilibrium after a disturbance.

  • Steady-State (Small Signal) Stability: Ability to maintain synchronism for small disturbances (e.g., small load changes). Analyzed by linearized swing equation.

  • Transient Stability: Ability to maintain synchronism after a large, sudden disturbance (e.g., fault, line outage). Analyzed by non-linear swing equation and Equal Area Criterion (EAC).

  • Rotor Angle Stability: Concerned with maintaining synchronism between all synchronous machines. Root cause of instability.

3.2 Swing Equation

  • Derivation: From Newton's 2nd law for rotor rotation.

$$ M \frac{d^2 \delta}{dt^2} = P_m - P_e = P_a $$

where:

*   $$\displaystyle M = 2H / \omega_s $$ (Inertia constant, kg-m² or MJ/MVA)

*   $\delta$ = Rotor angle (rad) relative to synchronously rotating reference.

*   $$\displaystyle P_m $$ = Mechanical power input (p.u.).

*   $$\displaystyle P_e $$ = Electrical power output (p.u.).

*   $$\displaystyle P_a $$ = Accelerating power (p.u.).
  • Physical Significance: $M$ represents the stored kinetic energy in the rotating mass. $$\displaystyle P_a $$ determines acceleration/deceleration of the rotor.

Linearized Swing Equation (for small δ):

$$ M \frac{d^2 (\Delta \delta)}{dt^2} + D \frac{d (\Delta \delta)}{dt} + \omega_s^2 \frac{\partial P_e}{\partial \delta} \Delta \delta = 0 $$

  • $D$ = Damping coefficient.

  • $$\displaystyle \frac{\partial P_e}{\partial \delta} $$ = Synchronizing power coefficient.

  • Steady-State Stability Limit: $$\displaystyle \frac{\partial P_e}{\partial \delta} > 0 $$. Maximum power transfer occurs at $$\displaystyle \frac{\partial^2 P_e}{\partial \delta^2} = 0 $$.

3.3 Equal Area Criterion (EAC)

  • Geometric Interpretation: For a single machine-infinite bus system, stability is determined by comparing the accelerating area ($$\displaystyle A_{acc} $$) and decelerating area ($$\displaystyle A_{dec} $$) under the $$\displaystyle P_e(\delta) $$ curve during and after a fault.

$$ A_{acc} = \int_{\delta_0}^{\delta_{cr}} (P_m - P_e) d\delta $$

$$ A_{dec} = \int_{\delta_{cr}}^{\delta_{max}} (P_e - P_m) d\delta $$

  • Condition for Stability: $$\displaystyle A_{acc} = A_{dec} $$ (system regains equilibrium). If $$\displaystyle A_{acc} > A_{dec} $$, machine loses synchronism.

  • Critical Clearing Angle ($$\displaystyle \delta_{cr} $$): Angle at fault clearing where $$\displaystyle A_{acc} = A_{dec} $$.

  • Critical Clearing Time ($$\displaystyle t_{cr} $$): Maximum fault duration for which system remains stable. Found by integrating swing equation numerically up to $$\displaystyle \delta_{cr} $$.

Example Problem (EAC): Generator delivers 50% of $$\displaystyle P_{max} $$ to infinite bus. Fault increases reactance to 500% of pre-fault value. Post-fault $$\displaystyle P_{max} $$ is 75% of original.

  1. Pre-fault: $$\displaystyle P_{e0} = 0.5 P_{max0} $$ at $$\displaystyle \delta_0 $$.
  1. During fault: $$\displaystyle P_{e,fault} = P_{max0}/5 = 0.2 P_{max0} $$ (since reactance 5x, $$\displaystyle P_{max} \propto 1/X $$).
  1. Post-fault: $$\displaystyle P_{e,post} = 0.75 P_{max0} $$.
  1. Calculate $$\displaystyle \delta_0 $$, $$\displaystyle \delta_1 $$ (fault on), $$\displaystyle \delta_2 $$ (fault cleared), $$\displaystyle \delta_3 $$ (max).
  1. Set $$\displaystyle A_{acc} = A_{dec} $$ to find $$\displaystyle \delta_{cr} $$ (which is $$\displaystyle \delta_2 $$).

3.4 Factors Affecting Stability

Steady-State Transient
System voltage level Fault type, location, duration
Transfer reactance (X) Clearing time ($$\displaystyle t_{cr} $$)
Generator excitation (AVR) System inertia (H)
Load characteristics Generator output ($$\displaystyle P_m $$)
Reactance of lines (X)
Use of high-speed reclosure, braking resistors, FACTS

3.5 Methods of Improving Stability

  • Steady-State: Use AVRs (increase $$\displaystyle P_{max} $$), reduce transfer reactance (parallel lines, series capacitors), improve power factor.

  • Transient:

    • Fast Fault Clearing: High-speed circuit breakers.

    • Single-Pole Switching: For single-line-to-ground faults, only faulty pole opens.

    • Braking Resistors: Insert resistance at generator terminals during fault to reduce acceleration.

    • FACTS Devices: SVC, STATCOM for dynamic voltage support; TCSC for reducing effective X.

    • Fast Governor Response: Fast valving.

    • High Inertia: More rotating mass.


4.0 FREQUENCY CONTROL & GOVERNOR MODELING

4.1 Necessity for Strict Frequency Control

  • Equipment: Frequency affects speed of synchronous motors, induction motors, turbines, clocks.

  • System Operation: Frequency is a real-time indicator of generation-load balance. Deviation indicates imbalance.

  • Loads: Many industrial processes (paper mills, petrochemicals) are frequency-sensitive.

  • Grid Codes: Strict limits (e.g., ±0.5 Hz in India) must be maintained.

4.2 Load Frequency Control (LFC) in Interconnected Systems

  • Primary (Governor) Control:

    • Action: Speed governor responds to frequency change Δf by adjusting turbine valve.

    • Characteristic: Droop (Speed Regulation) R = Δf / ΔP_m (%). Provides inherent, instantaneous but incomplete regulation. Load sharing between parallel generators is inversely proportional to R.

    • Limitation: Leaves a steady-state frequency error.

  • Secondary (ALFC) Control & Tie-Line Bias:

    • Area Control Error (ACE): ACE = ΔP_{tie} + B Δf

      • ΔP_{tie} = Net tie-line power deviation from scheduled.

      • B = Frequency Bias Factor (MW/Hz), chosen as area load-frequency characteristic (-D - 1/R).

    • Action: ACE is integrated (Integral Controller) to generate a setpoint change for the governor, bringing ACE to zero → eliminates frequency error and corrects tie-line power.

  • Modeling of Tie-Line Power Flow:

    For two areas, tie-line power from Area 1 to 2:

$$ P_{tie,12} = \frac{|V_1||V_2|}{X_{tie}} \sin(\delta_1 - \delta_2) $$

For small angle changes: `ΔP_{tie} = T_{12} Δδ`, where `T_{12}` is tie-line synchronizing coefficient.

4.3 Turbine Speed Governing System Modeling

  • Components: Speed Governor → Amplifier/Pilot Valve → Servomotor → Turbine.

  • Transfer Function Block Diagram:

    
    Δf → [1/(1+sT_g)] → ΔP_{m0} (Governor)
    
    ΔP_{m0} → [1/(1+sT_t)] → ΔP_m (Turbine)
    
    
    • T_g = Governor time constant (0.1-0.5 sec).

    • T_t = Turbine time constant (0.2-1.0 sec).

  • Governor Time Constant & Speed Regulation: R is the steady-state droop. T_g represents the delay in valve movement.

4.4 Inertia Constant (H) & System Inertia

  • Definition: H = (Stored Kinetic Energy at synchronous speed) / (Generator MVA base)

$$ H = \frac{0.5 J \omega_s^2}{S_{base}} \text{ (seconds or MJ/MVA)} $$

where `J` = moment of inertia (kg-m²), `ω_s` = synchronous speed (rad/s).
  • Physical Meaning: Time (in seconds) for which a generator can supply full load from its stored kinetic energy if all input is lost.

  • Equivalent Inertia Constant for Parallel Machines:

$$ H_{eq} = \frac{\sum (H_i \cdot S_{i,base})}{\sum S_{i,base}} $$

(Weighted average based on MVA ratings).

4.5 Numerical Problems

  • Frequency Drop with Governor Delay (H given):

    Problem: 100 MVA, 50 Hz alternator, H=4.5 kW-sec/kVA. Load drop of 25 MW at t=0. Governor delay T_g=0.6 sec. Find frequency at t=0.6 sec.

    Solution:

    1. Convert H: H = 4.5 kW-sec/kVA = 4.5 sec (since 1 kW-sec/kVA = 1 sec).

    2. Stored energy: KE = H * S_base = 4.5 * 100 = 450 MJ.

    3. During delay (0 to 0.6 sec), P_m constant = P_e0 (assume initial load = 0? Or need initial load?). Typically, assume initial P_m = P_e0. Sudden load drop ΔP = 25 MW.

    4. Accelerating power P_a = P_m - P_e = 0 - (-25) = +25 MW? Clarify: If load drops, P_e decreases. For constant P_m, P_a = P_m - P_e becomes positive (accelerating).

    5. Swing equation: M d²δ/dt² = P_a. M = 2H/ω_s.

    6. Integrate: Δω = (P_a * t) / (2H) (for constant P_a, small Δf).

    7. Δf = (f_s / (2H)) * ∫ P_a dt (in p.u. or consistent units).

    8. For 0 ≤ t ≤ T_g, P_a = ΔP_load (since P_m hasn't changed).

    9. Δf(0.6) = (ΔP * t) / (2H * S_base) in p.u. → convert to Hz.

    Key Formula:

$$ \Delta f (Hz) = \frac{f_s \cdot \Delta P (MW) \cdot t (sec)}{2 \cdot H (MJ/MVA) \cdot S_{base} (MVA)} $$

Plug: `Δf = (50 * 25 * 0.6) / (2 * 4.5 * 100) = 750 / 900 = 0.833 Hz drop`. New freq = 49.167 Hz.
  • Two-Area Load Sharing: Generation shares inversely proportional to their speed regulations R. If R_A and R_B, then P_{GA} / P_{GB} = R_B / R_A for a given total load and tie-line schedule.

  • Energy Stored in Rotor: KE = H * S_base (in MJ if H in MJ/MVA, S_base in MVA).


5.0 VOLTAGE CONTROL & REACTIVE POWER MANAGEMENT

5.1 Relationship between Reactive Power Flow and Voltage Profile

  • Phasor Diagram & Equation: For a line sending end voltage V_s, receiving end V_r, sending angle δ_s, receiving δ_r.

$$ V_r^2 = (V_s \cos \delta + I_r X)^2 + (V_s \sin \delta + I_r R)^2 $$

Neglecting R (high voltage lines):

$$ V_r \approx V_s - \frac{Q_r X}{V_s} $$

(for small δ, inductive load Q_r > 0)

**Key Insight:** Voltage drop `ΔV ≈ (Q_r X) / V_s`. **Reactive power flow (Q) is the dominant factor** in voltage variation along a transmission line.
  • Reactive Power Balance: Q_gen - Q_loss - Q_load = ΔQ_shunt (capacitors/ reactors). Voltage rises if Q_gen > Q_load + losses.

5.2 Generation and Absorption of Reactive Power

Component Generation (Leading) Absorption (Lagging)
Synchronous Generator Over-excited (E > V) Under-excited (E < V)
Transmission Line Capacitive charging (always generates, esp. no-load) Inductive reactance (absorbs)
Transformer No generation (small magnetizing) Absorbs (magnetizing current)
Loads Capacitive loads (rare) Inductive loads (majority)

5.3 Methods of Voltage Control

  1. Generator Voltage Control (Excitation Systems): Primary control. AVR adjusts field current to maintain terminal voltage.

  2. Tap Changing Transformers:

    • OLTC (On-Load Tap Changer): Continuous voltage control at substations.

    • Off-Load Tap Changer: For coarse, infrequent adjustments.

  3. Shunt Compensation:

    • Shunt Capacitors: Inject Q (raise voltage). Switched in blocks.

    • Shunt Reactors: Absorb Q (lower voltage). Used for light-load voltage control on long lines.

  4. Series Compensation: Series capacitors reduce effective line reactance X, increasing power transfer capability and improving voltage profile.

5.4 Protection and Absorption of Reactive Power

  • Need for Balance: Excess reactive power causes over-voltages (esp. light load); deficiency causes voltage collapse.

  • Methods for Absorption (Q_consumer):

    • Shunt Reactors: Fixed or switched.

    • SVC (Static Var Compensator): Thyristor-controlled reactor (TCR) + Thyristor-switched capacitor (TSC). Fast, continuous.

    • STATCOM: Voltage-source converter based. Better performance at low voltages.

    • Synchronous Condensers: Over-excited synchronous motors running without load. Good inertia support.

  • Methods for Support/Generation (Q_producer):

    • Shunt Capacitors: Switched.

    • SVC/STATCOM: Can both generate and absorb.

    • Synchronous Condensers: Over-excited.

    • Generator Over-excitation: Increase field current (within limits).

[!TIP] Exam Focus: Be able to draw the V-I characteristic of SVC and STATCOM. Know that voltage control is essentially reactive power control.


6.0 EXCITATION SYSTEMS

6.1 Need and Objectives

  • Voltage Control: Maintain generator terminal voltage or system voltage at a bus.

  • Stability Enhancement: Increase steady-state stability limit ($$\displaystyle P_{max} \propto E V / X $$). Improve transient stability by maintaining voltage during faults.

  • Reactive Power Sharing: Control reactive power output in parallel operation.

6.2 Types of Excitation Systems

  1. DC Excitation System: DC generator (exciter) driven by motor or turbine. Amplidyne is a high-gain DC amplifier used as voltage regulator. Largely obsolete.

  2. AC Static (Brushless) Excitation System:

    • Functional Block Diagram:

      
      AVR → Rotating Diode Rectifier (on shaft) → Generator Field
      
      
    • Description: AC exciter (on same shaft) produces AC, rectified by rotating diodes, supplies DC to main generator field. No brushes/slip rings. Reliable, low maintenance.

  3. Modern Static Excitation System:

    • Block Diagram:

      
      AVR → Thyristor Rectifier (static) → Generator Field
      
      
    • Description: Uses transformer from generator terminals, thyristor bridge provides controlled DC. Fast response, precise control. Often includes Power System Stabilizer (PSS).

6.3 Functional Block Diagram & Elements

  • Exciter: Source of DC power (DC gen, AC gen+rectifier, static transformer+thyristor).

  • Automatic Voltage Regulator (AVR): Compares terminal voltage V_t with reference V_ref, amplifies error, controls exciter output. Main control loop.

  • Power System Stabilizer (PSS): Auxiliary control. Takes input (Δω or ΔP) and produces a signal to AVR to damp power oscillations (rotor angle swings) by modulating field voltage.

6.4 Limiting Features in Excitation Systems

To protect generator from overheating and instability:

  • Over-excitation Limit (OEL): Prevents field current/thermal overload (V/Hz or field current limit).

  • Under-excitation Limit (UEL): Prevents instability from lagging power factor operation (stability limit).

  • V/Hz Limit (Volts/Hz): Prevents core saturation (over-fluxing) during low-frequency/high-voltage conditions.

  • Stator Current Limit: Prevents stator overheating.


7.0 ECONOMIC OPERATION OF POWER SYSTEMS

7.1 Economic Dispatch Problem

  • Definition: Allocate total load demand among available generating units to minimize total fuel cost while satisfying constraints (generation limits, power balance).

  • Input-Output Characteristics (Heat Rate Curve): F_i(P_i) = Fuel cost ($/hr) for generator i at output P_i (MW). Usually quadratic: F_i = a_i + b_i P_i + c_i P_i^2.

7.2 Economic Dispatch without Transmission Losses

  • Lagrangian Multiplier Method:

    Minimize ∑ F_i(P_i) subject to ∑ P_i = P_D.

    Lagrangian: L = ∑ F_i(P_i) + λ (P_D - ∑ P_i)

    Coordination Equation: ∂L/∂P_i = 0 → F_i'(P_i) = λ

    • λ = Incremental Fuel Cost ($/MWh). At optimum, all units operate at same λ.
  • Solution: For each unit, plot F_i'(P_i) vs P_i. Find intersection with common λ line satisfying ∑ P_i = P_D.

7.3 Economic Dispatch considering Transmission Losses

  • Loss Coefficients (B-coefficients): Approximate transmission loss as:

$$ P_{loss} = \sum_{i} \sum_{j} B_{ij} P_i P_j + \sum_{i} B_{i0} P_i + B_{00} $$

`B_ij` are loss coefficients (symmetric, `B_ii > 0`, `B_ij < 0`), determined from system impedance matrix.
  • Penalty Factor (λ_i):

$$ \lambda_i = \frac{\lambda}{1 - \frac{\partial P_{loss}}{\partial P_i}} = \frac{\lambda}{1 - (2 \sum_j B_{ij} P_j + B_{i0})} $$

*   At optimum: `F_i'(P_i) = λ_i` (not λ). Units with higher loss contribution (large ∂P_loss/∂P_i) have higher effective incremental cost.
  • Iterative Solution Procedure:

    1. Assume initial P_i (e.g., equal sharing), calculate P_loss and ∂P_loss/∂P_i.

    2. Calculate λ_i for each unit.

    3. Find new P_i from F_i'(P_i) = λ_i.

    4. Check ∑ P_i - P_D - P_loss ≈ 0. If not, repeat from step 1.

Example Problem: Given two units with cost functions and B-coefficients, find optimal dispatch.

Steps:

  1. Write F_1' = b_1 + 2c_1 P_1, F_2' = b_2 + 2c_2 P_2.
  1. Calculate ∂P_loss/∂P_1 = 2B_11 P_1 + B_12 P_2 + B_10.
  1. Set F_1' / (1 - ∂P_loss/∂P_1) = F_2' / (1 - ∂P_loss/∂P_2) = λ.
  1. Solve simultaneous equations with P_1 + P_2 = P_D + P_loss(P_1,P_2).
  1. Iterate until convergence.

8.0 ENERGY PRICING & TRANSMISSION SERVICE

8.1 Pricing of Energy (Generation Side)

  • Marginal Cost: Cost of producing one additional MWh. Equals incremental fuel cost (λ) at optimal dispatch. Basis for spot pricing.

  • Average Cost: Total cost / total MWh. Includes fixed (capital) and variable (fuel, O&M) costs.

  • Components of Energy Price:

    • Fuel Cost: Variable, major component.

    • O&M Cost: Fixed and variable.

    • Capital Recovery: Fixed charge (interest, depreciation).

    • Profit Margin: In deregulated markets.

    • Ancillary Services: Cost of regulation, spinning reserve.

8.2 Pricing of Transmission Service (Wheeling Charges)

  • Need: In open access, transmission owner must recover fixed costs (investment, maintenance) for wheeling (transmitting) third-party power.

  • Methods:

    • Postage Stamp: Flat fee per MW of wheeled power, regardless of distance. Simple, non-economic.

    • Contract Path: Charge based on agreed path (distance × rate). Ignores physical flows.

    • MW-Mile: Charge = Rate ($/MW-mile) × MW × Miles. Better reflects usage.

    • Marginal Cost Pricing: Charge based on marginal cost of using the network (congestion cost). Economically efficient but complex.

  • Embedded Cost vs. Marginal Cost:

    • Embedded Cost: Allocates historical/ sunk costs (depreciation, fixed O&M). Used for "revenue requirement".

    • Marginal Cost: Cost of serving one more customer. Provides efficient price signals but may not cover fixed costs.


9.0 SYNTHESIS & APPLICATION OF CONCEPTS

9.1 Interrelationship: Frequency, Real Power, Governor Control

  • Frequency (f) ∝ Net Rotating Speed.

  • Real Power Imbalance (ΔP = P_m - P_e) causes Accelerating Power (P_a) → changes Rotor Angle (δ) and Frequency (f).

  • Governor Control (Primary) adjusts P_m in response to Δf (droop characteristic). ALFC (Secondary) adjusts setpoints to bring f and tie-line power to scheduled values.

  • Key Equation: Swing equation links P_a to d²δ/dt²; frequency deviation Δf ∝ dδ/dt.

9.2 Interrelationship: Voltage, Reactive Power, Excitation/Reactive Compensation

  • Voltage (V) at a bus is determined by Reactive Power (Q) balance.

  • Reactive Power Flow causes voltage drops (ΔV ∝ Q X / V).

  • Excitation System controls generator E (internal voltage) → controls Q output → controls local V.

  • Shunt Capacitors/Reactors, SVC, STATCOM directly inject/absorb Q → control V profile.

  • Series Capacitors reduce X → improve V profile and power transfer.

9.3 Integrated View: Load Flow, Stability, Control Studies

  • Load Flow: Provides steady-state operating point (V, δ, P, Q) for a dispatch. This is the initial condition for stability studies.

  • Stability Studies (Transient): Start from load flow solution, apply a disturbance (fault), simulate using swing equation (for each machine) coupled with network algebraic equations (from Ybus). Requires dynamic models of governors (turbine-governor) and exciters (AVR).

  • Control Systems: Governor and AVR models are integral parts of transient stability simulation. Their settings (R, time constants, limits) directly affect stability margins.

  • Economic Dispatch: Determines P_i setpoints used in load flow. Must consider transmission losses (B-coefficients) which come from network model (Ybus).

9.4 Application of EAC in Multi-Machine Systems (Conceptual Extension)

  • For a multi-machine system, EAC is applied between each machine and the system center of inertia (COI).

  • COI Angle (δ_COI): Weighted average of all machine angles.

  • Swing Equation relative to COI:

$$ M_{total} \frac{d^2 \delta_{COI}}{dt^2} = \sum (P_{mi} - P_{ei}) = 0 \text{ (if COI is inertial frame)} $$

  • For machine i: M_i d²δ_i/dt² = P_{mi} - P_{ei} - (M_i/M_total) Σ(P_m - P_e).

  • Multi-Machine EAC: Plot P_{ei} - P_{mi} vs δ_i - δ_COI for each machine. Stability requires all machines to have A_acc = A_dec relative to COI. A machine losing synchronism with COI means system instability.

[!TIP] Exam Synthesis: Be ready to explain how a load flow solution feeds into a transient stability study, and how governor/AVR settings from control studies affect the stability result.

Go to where you left off?

Quick Add to Notes

Save questions, your own notes and screenshots into notes filed by unit. It takes a free account.

Create free account

Have an account? Log in